131
-
'11 • SCM-SM-110
Error code
Remote controller:
LED
Green
Red
Indoor
Content
E53
Suction pipe temperature
sensor anomaly
Keeps flashing
Stays OFF
Outdoor
–
8
times flash
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Is
the suction pipe
temperature sensor connector
connected properly?
YES
Is the
characteristics of the
suction pipe temperature
sensor
OK?
NO
For the characteristics of suction pipe
temperature sensor, see the following graph.
YES
Temperature-resistance characteristics
15
10
5
0
10
30 40
20
50
NO
Temperature sensor resistance (k
Ω
)
Temperature (°C)
5k
Ω
at 25°C
(Broken wire)
(Shot circuit)
Correct connector.
Defective suction pipe
temperature sensor
➞
Replace.
Defective outdoor sub
PCB
➞
Replace.
(Defective suction pipe
temperature sensor input
circuit)
2. Error detection method
Detection of anomalously low
temperature (resistance) on
suction pipe temperature sensor
3. Condition of Error displayed
• When the temperature sensor
detects -55 °C or lower for 5
seconds continuously within
2 minutes to 2 minutes 20
seconds after the compressor
ON, the compressor stops.
After 3-minutes delay, the
compressor starts again
automatically, but if this
anomalous temperature is
detected 3 times within 40
minutes.
• When -55 °C or lower is
detected for within 20 second
after power ON.
4. Presumable cause
• Defective outdoor sub PCB
• Broken sensor harness or
temperature sensing section
(Check molding.)
• Disconnected wire connection
(connector)
Note:
Содержание SCM100ZJ-S1
Страница 64: ...63 11 SCM SM 110 Service data record form 55...
Страница 194: ...193 11 SCM SM 110 4 Ceiling cassette 4way compact type FDTC refer to page 157 to 172...
Страница 198: ...197 11 SCM SM 110 PJAO12D786...
Страница 223: ...222 11 SCM SM 110 4 way valve coil 1 Disconnect the connector 2 Loosen a screw and remove the coil Connector Screw Coil...
Страница 237: ...236 11 SCM SM 110 EEVB EEVC EEVA EEVD MARKING GREEN BLUE RED WHITE EEV A EEV D 46 WH 46 46 46 M YE OR BL RD Input 12VDC...