129
-
'11 • SCM-SM-110
Error code
Remote controller:
LED
Green
Red
Content
Indoor Keeps flashing Stays OFF
E51
Power transistor anomaly
(
Model SCM40, 45, 50, 60, 71, 80
)
Outdoor
–
1
time flash
Error code
Remote controller: E51
LED
Green
Red
Indoor
Content
Power transistor error
Keeps flashing Stays Off
1. Applicable model
5. Troubleshooting
Model SCM40, 45, 50, 60, 71, 80
only
Diagnosis
Countermeasure
2. Error detection method
3.Condition of Error displayed
4. Presumable cause
Note:
If the power transistor primary
current exceeds the setting value
for 3 seconds, the compressor
stops.
Power transistor primary current
• Faulty outdoor main PCB
• Dust on outdoor main PCB
• Blown F2 fuse
Check soldered
surfaces on the outdoor main PCB for
foreign matter like dust,
fouling,etc.
Isn
’t F2 fuse
(250V, 20A)blown?
Remove foreign matter
like dust, fouling, etc.
Replace fuse.
Defective outdoor main
PCB
ª
Replace.
YES
YES
NO
NO
Содержание SCM100ZJ-S1
Страница 64: ...63 11 SCM SM 110 Service data record form 55...
Страница 194: ...193 11 SCM SM 110 4 Ceiling cassette 4way compact type FDTC refer to page 157 to 172...
Страница 198: ...197 11 SCM SM 110 PJAO12D786...
Страница 223: ...222 11 SCM SM 110 4 way valve coil 1 Disconnect the connector 2 Loosen a screw and remove the coil Connector Screw Coil...
Страница 237: ...236 11 SCM SM 110 EEVB EEVC EEVA EEVD MARKING GREEN BLUE RED WHITE EEV A EEV D 46 WH 46 46 46 M YE OR BL RD Input 12VDC...