134
-
'11 • SCM-SM-110
Error code
Remote controller:
LED
Green
Red
Content
Indoor Keeps flashing Stays OFF
E58
Current safe stop
(
Model SCM40, 45, 50, 60, 71, 80
)
Outdoor
–
3
times flash
Error code
Remote controller: E58
LED
Green
Red
Indoor
Outdoor
―
Content
Current safe stop
(Model SRC40 - 60)
Keeps flashing Stays Off
3 time flash
1. Applicable model
5. Troubleshooting
Model SCM40, 45, 50, 60, 71, 80
only
When the current safe control
has operated at the compressor
speed of 30 rps or under:
Same as above
• Excessive refrigerant amount
• Indoor,outdoor unit installation
spaces
• Faulty compressor
• Defective outdor air temp.
sensor
• Defective outdoor main PCB
Diagnosis
Countermeasure
2. Error detection method
3.Condition of Error displayed
4. Presumable cause
Note:
Is outdoor
ventilation condition
good ?
Inspect
outdor air temp.
sensor
Is the refrigerant
amount nomal ?
Adjust the refrigerant
amount properly.
Secure space for inlet and
outlet.
Replace compressor.
Replace sensor.
Defective outdoor main
PCB
¡
Replace.
(Defective outdor air temp.
sensor input circuit)
Inspect
compressor
YES
YES
YES
NO
NO
NO
NO
NO
Содержание SCM100ZJ-S1
Страница 64: ...63 11 SCM SM 110 Service data record form 55...
Страница 194: ...193 11 SCM SM 110 4 Ceiling cassette 4way compact type FDTC refer to page 157 to 172...
Страница 198: ...197 11 SCM SM 110 PJAO12D786...
Страница 223: ...222 11 SCM SM 110 4 way valve coil 1 Disconnect the connector 2 Loosen a screw and remove the coil Connector Screw Coil...
Страница 237: ...236 11 SCM SM 110 EEVB EEVC EEVA EEVD MARKING GREEN BLUE RED WHITE EEV A EEV D 46 WH 46 46 46 M YE OR BL RD Input 12VDC...