126
-
'11 • SCM-SM-110
Error code
Remote controller:
LED
Green
Red
Outdoor
Content
–
4 times flash
Indoor Keeps flashing Stays OFF
E45
Outdoor sub PCB
communication error
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
YES
Replace the outdoor main PCB.
NO
YES
YES
Is the connector
connection between the outdoor
main PCB and the outdoor sub
PCB OK?
Is the power supply voltage OK?
Is the
communication wire
between the main PCB and the outdoor sub
PCB connected properly?
Is normal state restored?
YES
NO
NO
NO
Correct connector.
Check why power is not
supplied to outdoor sub
PCB.
Connect communication
wire securely.
Defective outdoor sub PCB
➞
Replace.
Malfunction by temporary
noise
2. Error detection method
Detected communication error
of more than 15 seconds 4 times
in 15 minutes.
3. Condition of Error displayed
When communication is not
established between the outdoor
sub PCB and the outdoor main
PCB.
4. Presumable cause
• Defective sub PCB
• Defective connector between
the outdoor main PCB and
outdoor sub PCB
• Defective outdoor main
(control) PCB
Note:
Содержание SCM100ZJ-S1
Страница 64: ...63 11 SCM SM 110 Service data record form 55...
Страница 194: ...193 11 SCM SM 110 4 Ceiling cassette 4way compact type FDTC refer to page 157 to 172...
Страница 198: ...197 11 SCM SM 110 PJAO12D786...
Страница 223: ...222 11 SCM SM 110 4 way valve coil 1 Disconnect the connector 2 Loosen a screw and remove the coil Connector Screw Coil...
Страница 237: ...236 11 SCM SM 110 EEVB EEVC EEVA EEVD MARKING GREEN BLUE RED WHITE EEV A EEV D 46 WH 46 46 46 M YE OR BL RD Input 12VDC...