-
112
-
'11 • SCM-SM-110
Error code
Remote controller:
LED
Green
Red
Indoor
Content
E16
Indoor fan motor anomaly
(
FDTC and FDUM series
)
Keeps flashing 1 time flash
Outdoor
–
Stays OFF
1. Applicable model
5. Troubleshooting
FDTC and FDUM series only
Diagnosis
Countermeasure
NO
YES
YES
Does any
foreign material
intervene in rotational area
of fan propeller?
Is DC280V
detected between
�
-
�
of
fan motor connector
CNM?
Is it normalized?
Does the fan
rotate smoothly when turned
by hand?
YES
NO
NO
NO
YES
(
1
)
Note (1)
�
for GND
NO
YES
Power supply reset
Is the fuse F202
(
FDUM: F3
)
blown?
Remove foreign material.
Replace the fan motor.
Check power voltage.
Replace faulty fan motor
and power PCB.
Replace fan motor. (If the
error persists after replacing
the fan motor, replace the
indoor control PCB.)
Malfunction by temporary
noise
2. Error detection method
Detected by rotation speed of
indoor fan motor
3. Condition of Error displayed
When actual rotation speed of
indoor fan motor drops to lower
than 200rpm for 30 seconds
continuously, the compressor
and the indoor fan motor
stop. After 2-seconds, it starts
again automatically, but if this
error occurs 4 times within
60 minutes after the initial
detection.
4. Presumable cause
• Defective indoor power PCB
• Foreign material at rotational
area of fan propeller
• Defective fan motor
• Dust on control PCB
• Blown fuse
• External noise, surge
Note:
Содержание SCM100ZJ-S1
Страница 64: ...63 11 SCM SM 110 Service data record form 55...
Страница 194: ...193 11 SCM SM 110 4 Ceiling cassette 4way compact type FDTC refer to page 157 to 172...
Страница 198: ...197 11 SCM SM 110 PJAO12D786...
Страница 223: ...222 11 SCM SM 110 4 way valve coil 1 Disconnect the connector 2 Loosen a screw and remove the coil Connector Screw Coil...
Страница 237: ...236 11 SCM SM 110 EEVB EEVC EEVA EEVD MARKING GREEN BLUE RED WHITE EEV A EEV D 46 WH 46 46 46 M YE OR BL RD Input 12VDC...