233
-
'11 • SCM-SM-110
TB5
TB6
TB7
TB3
TB4
Locking support
PCB3
TB5
TB6
Faston connectoes
Sensor
TB7
TB3
TB4
PCB5
Locking
support
LACT
Screw
Diode stack
1. Dismount the 1st layer
according to the procedure
for control PCB (PWB1) and
Sub PCB (PWB4).
2. Loosen 5 screws and
disconnect the cables of
TB3 - TB7.
3. Pinch the head of locking
supports (4 pieces) and
remove the N/F PCB (PWB5).
Note: Be sure to do this work
after elapsing 3 minutes
from power OFF.
1. Dismount the 1st layer
according to the procedure
for control PCB (PWB1) and
Sub PCB (PWB4).
2. Loosen 5 screws and
disconnect the cables of
TB3 - TB7.
3. Pinch the head of locking
supports (4 pieces) and
remove the N/F PCB
(PWB3).
Note: Be sure to do this work
after elapsing 3 minutes
from power OFF.
Active Filter (LACT) and Diode Stack (DS) on the 2nd layer
Noise filter PCB (PWB3) on the back side lower of the 1st layer
Noise filter PCB (PWB5) on the back side upper of the 1st layer
1. Active Filter
Disconnect the faston
connectors (6 pieces) and
sensor (1 piece).
And then loosen 2 screws
and remove LACT.
2. Diode Stack
Disconnect all connectors
(4 pieces) and loosen 2
screws.
And then remove diode
stack.
Содержание SCM100ZJ-S1
Страница 64: ...63 11 SCM SM 110 Service data record form 55...
Страница 194: ...193 11 SCM SM 110 4 Ceiling cassette 4way compact type FDTC refer to page 157 to 172...
Страница 198: ...197 11 SCM SM 110 PJAO12D786...
Страница 223: ...222 11 SCM SM 110 4 way valve coil 1 Disconnect the connector 2 Loosen a screw and remove the coil Connector Screw Coil...
Страница 237: ...236 11 SCM SM 110 EEVB EEVC EEVA EEVD MARKING GREEN BLUE RED WHITE EEV A EEV D 46 WH 46 46 46 M YE OR BL RD Input 12VDC...