221
-
'11 • SCM-SM-110
EEV coils
1. Remove the faulty EEV coil
and disconnect the connector.
Note:
1) When disconnecting the
connector, be sure to
check the color marked
on the top of coil and
the color of the connector.
2) When replace to a new
coil, be sure to insert the
socket attached to the coil
to the pipe correctly.
EEVD
EEVC
EEVB
EEVA
Marking color
GREEN
GREEN
BLUE
BLUE
RED
RED
WHITE
WHITE
Socket