'11 • SCM-SM-110
(18) Serial signal transmission error protection
(a) Purpose:
(b) Detail of operation:
(19) Rotor lock (Model SCM40, 45, 50, 60, 71, 80 only)
(20) Outdoor fan motor protection
(21) Outdoor fan control at low outdoor temperature
Cooling
Model SCM40, 45, 50, 60, 71, 80
(a) Operating conditions:
(b) Detail of operation:
(c) Reset conditions:
Outdoor air temperature > 10˚C
Outdoor air temperature <= 10˚C
Outdoor fan
Outdoor air temperature > 16˚C
Outdoor air temperature <= 16˚C
Lower limit speed
Tho-A
Tho-R
Tho-R
Tho-R
Tho-A
Model SCM100, 125
(a) Operating conditions:
(b) Detail of operation:
Outdoor air temperature > 10˚C
Outdoor air temperature <= 10˚C
Outdoor fan
3rd
Tho-A