'11 • SCM-SM-110
2) Remote operation input
Remote operation input connector (CnT-6) is provided on the indoor control PCB.
However remote operation by CnT-6 is not effective, when “Center mode” is selected by center controller.
In case of plural unit (twin, triple, double twin), remote operation input to CnT-6 on the slave indoor unit is invalid.
Only the “LEVEL INPUT” is acceptable for external input
, however when the indoor function setting of “Level
input (Factory default)” or “Pulse input” is selected by the function for “External input” of the wired remote controller,
operation status will be changed as follows.
a) In case of “Level input” setting (Factory default)
Input signal to CnT-6 is OFF→ON …… unit ON
Input signal to CnT-6 is ON→OFF …… unit OFF
Operation is not inverted.
Note: The latest operation has priority
It is available to operate/stop by remote controller or center controller
b) In case of “Pulse input” setting (Local setting)
It is effective only when the input signal to CnT-6 is changed OFF→ON, and at that time unit operation [ON/OFF] is
inverted.
3) Remote operation
a) In case of multiple units (Max. 16 indoor units group) are connected to one wired remote controller
When the indoor function setting of wired remote controller for “External control set” is changed from “Individual
(Factory default)” to “ For all units”, all units connected in one wired remote controller system can be controlled by
external operation input.
Ex. Indoor units =
+①+②+③+④+⑤
・・・・ + + + ≦
16 units
R
①
②
③
④
⑤
Outdoor unit
SCM**ZJ type
Outdoor unit
SCM**ZJ type
Indoor unit
Remote controller
Wirings between
outdoor unit and
indoor units
C
D
E
F
C
D
E
F
0
0
ON
ON
OFF
OFF
OFF
ON
ON
ON
ON
Remote
controller OFF
Remote
controller ON
OFF
OFF
OFF
CnT-6 input
Unit A
Unit B
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
OFF
OFF
CnT-6 input
Unit A
Unit B
Remote
controller OFF
Remote
controller ON
ON
ON
OFF
OFF
ON
OFF
OFF
CnT-6 input
Unit A
Unit B
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
ON
ON
ON
OFF
OFF
CnT-6 input
Unit A
Unit B
• Model FDTC and FDEN
• Model FDUM
• Model FDTC and FDEN
• Model FDUM
Содержание SCM100ZJ-S1
Страница 64: ...63 11 SCM SM 110 Service data record form 55...
Страница 194: ...193 11 SCM SM 110 4 Ceiling cassette 4way compact type FDTC refer to page 157 to 172...
Страница 198: ...197 11 SCM SM 110 PJAO12D786...
Страница 223: ...222 11 SCM SM 110 4 way valve coil 1 Disconnect the connector 2 Loosen a screw and remove the coil Connector Screw Coil...
Страница 237: ...236 11 SCM SM 110 EEVB EEVC EEVA EEVD MARKING GREEN BLUE RED WHITE EEV A EEV D 46 WH 46 46 46 M YE OR BL RD Input 12VDC...