'11 • SCM-SM-110
() Unit No. may be set at random unless duplicated, it should be better to set orderly like 0, , …, F to avoid mistake.
)
Display to the remote controller
a)
Center or each remote controller basis, heating preparation: the youngest unit No. among the operating units in the
remote mode (or the center mode unless the remote mode is available) is displayed.
b)
Inspection display, filter sign: Any of unit that starts initially is displayed.
c)
Confirmation of connected units
Pressing “AIR CON No.” button on the remote controller displays the indoor unit address. If “
▲
” “
▼
” button is
pressed at the next, it is displayed orderly starting from the unit of youngest No.
d)
In case of anomaly
i) If any anomaly occurs on a unit in a group (a protective function operates), that unit stops with the anomalous
stop but any other normal units continue to run as they are.
ii) Signal wiring procedure
Signal wiring between indoor and outdoor units should be made on each unit same as the normal wiring.
For the group control, lay connect with sires wiring between rooms using terminal blocks (X, Y) of remote
controller.
Connect the remote controller communication wire separately from the power supply wire or wires of other
electric devices (AC0V or higher).
(s) High ceiling control
In the case of indoor unit installed in a higher ceiling room, the airflow volume mode control can be changed with the wired
remote controller indoor unit function “FAN SPEED SET”.
-
-
-
-
-
-
-
PHi - Hi
PHi - Me
PHi - Hi - Me
STANDARD
HIGH SPEED1, 2
FAN SPEED SET
Hi - Lo
Hi - Me
Hi - Me - Lo
PHi - PHi - Hi - Me
PHi - Hi - Me - Lo
Indoor unit airflow setting
Fan tap
Note () Factory default is Standard.
() At the hot-start and heating thermostat OFF, or other, the indoor unit fan is operated at the low speed tap of each setting.
() This function is not able to be set with wireless remote controls or simple remote control (RCH-E)
(t)
Abnormal temperature thermistor (return air/indoor heat exchanger) wire/short-circuit detection
1) Broken wire detection
When the return air temperature thermistor detects -20°C or lower or the heat exchanger temperature thermistor detect
-40°C or lower for 5 seconds continuously, the compressor stops. After a 3-minute delay, the compressor restarts but,
if it is detected again within 60 minutes after the initial detection for 6 minutes continuously, stops again (the return air
temperature thermistor: E7, the heat exchanger temperature thermistor: E6).
2) Short-circuit detection
If the heat exchanger temperature thermistor detects 70°C or higher for 5 seconds continuously at 2 minutes and 20
seconds after the compressor ON during cooling operation, the compressor stops (E6).
R
0
1
2
3
4
5
Outdoor unit
SCM**ZJ type
Outdoor unit
SCM**ZJ type
Indoor unit
Remote controller
Wirings between
outdoor unit and
indoor units
C
D
E
F
SW2 : For setting of 0 – 9, A – F
Содержание SCM100ZJ-S1
Страница 64: ...63 11 SCM SM 110 Service data record form 55...
Страница 194: ...193 11 SCM SM 110 4 Ceiling cassette 4way compact type FDTC refer to page 157 to 172...
Страница 198: ...197 11 SCM SM 110 PJAO12D786...
Страница 223: ...222 11 SCM SM 110 4 way valve coil 1 Disconnect the connector 2 Loosen a screw and remove the coil Connector Screw Coil...
Страница 237: ...236 11 SCM SM 110 EEVB EEVC EEVA EEVD MARKING GREEN BLUE RED WHITE EEV A EEV D 46 WH 46 46 46 M YE OR BL RD Input 12VDC...