106
-
'11 • SCM-SM-110
Error code
Remote controller:
LED
Green
Red
Indoor
Content
E5
Communication error during operation
Keeps flashing
2
times flash
Outdoor
–
6
times flash
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Has the remote
controller LCD returned to
normal state?
YES
NO
Is the
connection of signal
wires at the outdoor unit
side OK?
Is the
connection of signal
wires between indoor-outdoor
units OK?
Note (1) Inspect faulty connections (disconnection,
looseness) on the outdoor unit terminal block.
Power reset
Note (2) Check for faulty connection or breakage of
signal wires between indoor-outdoor units.
YES
NO
YES
NO
Repair signal wires.
Repair signal wires.
Defective outdoor sub
PCB (Defective network
communication circuit)
➞
Replace.
Unit is normal.
(Malfunction by temporary
noise, etc.)
2. Error detection method
When normal communication
between indoor and outdoor
unit is interrupted for more than
2 minutes.
3. Condition of Error displayed
Same as above is detected
during operation.
4. Presumable cause
• Unit No. setting error
• Broken remote controller wire
• Faulty remote controller wire
connection
• Faulty outdoor sub PCB
Note:
Содержание SCM100ZJ-S1
Страница 64: ...63 11 SCM SM 110 Service data record form 55...
Страница 194: ...193 11 SCM SM 110 4 Ceiling cassette 4way compact type FDTC refer to page 157 to 172...
Страница 198: ...197 11 SCM SM 110 PJAO12D786...
Страница 223: ...222 11 SCM SM 110 4 way valve coil 1 Disconnect the connector 2 Loosen a screw and remove the coil Connector Screw Coil...
Страница 237: ...236 11 SCM SM 110 EEVB EEVC EEVA EEVD MARKING GREEN BLUE RED WHITE EEV A EEV D 46 WH 46 46 46 M YE OR BL RD Input 12VDC...