Control mode
4.3.2
Change the control method (Pr. 80, Pr. 81, Pr. 451, Pr. 800)
(1) Setting of the motor capacity and the number of motor poles (
Pr. 80, Pr. 81
)
⋅
Motor specifications(the motor capacity and the number of motor poles) must be set to select advanced magnetic
flux vector control, real sensorless vector control or vector control.
⋅
Set the motor capacity (kW) in
Pr. 80 Motor capacity
and set the number of motor poles in
Pr. 81 Number of motor
poles
.
(2) Selection of control method and control mode
⋅
Select the inverter control method for V/F control, advanced magnetic flux vector control (speed control), real
sensorless vector control (speed control, torque control) and vector control (speed control, torque control, and
position control).
* Control method is V/F control regardless of the setting value of
Pr. 800
when "9999" is set in
Pr. 80
Motor capacity
or
Pr. 81
Number of motor poles
.
Set when selecting the advanced magnetic flux vector control, real sensorless vector control or vector control.
Select a control mode from speed control mode, torque control mode and position control mode under real
sensorless vector control or vector control. The initial value is V/F control.
Select a control method using
Pr. 800 (Pr. 451) Control method selection
.
Each control method can be switched using a method switching signal (MC).
Parameter
Number
Name
Initial
Value
Setting Range
Description
80
Motor capacity
9999
01800 or less
0.4 to 55kW
Set the applied motor capacity.
02160 or more 0 to 3600kW
9999
V/F control
81
Number of motor poles
9999
2, 4, 6, 8, 10
Set the number of motor poles.
12, 14, 16, 18, 20
X18 signal-ON:V/F control
Set 10 + number
of motor poles
9999
V/F control
800
Control method
selection
20
0 to 5
Vector control
9
Vector control test operation
10, 11, 12
Real sensorless vector control
20
V/F control (advanced magnetic flux vector control)
451
Second motor control
method selection
9999
10, 11, 12
Real sensorless vector control
20, 9999
V/F control (advanced magnetic flux vector control)
REMARKS
⋅
Setting number of motor poles in
Pr. 81
changes the
Pr. 144 Speed setting switchover
setting automatically. (Refer to
page
242
.)
Pr. 80,
Pr. 81
Setting
Pr. 800
Setting
Pr. 451
Setting
Control Method
Control Mode
Remarks
Other
than
9999
0
⎯
Vector control
Speed control
⎯
1
⎯
Torque control
⎯
2
⎯
Speed control-torque control
switchover
MC ON: Torque control
MC OFF: Speed control
3
⎯
Position control
⎯
4
⎯
Speed control-position
control switchover
MC ON: Position control
MC OFF: Speed control
5
⎯
Position control-torque
control switchover
MC ON: Torque control
MC OFF: Position control
9
⎯
Vector control test operation
10
Real sensorless vector
control
Speed control
⎯
11
Torque control
⎯
12
Speed control-torque control
switchover
MC ON: Torque control
MC OFF: Speed control
20
(
Pr. 800
initial value)
Advanced magnetic flux
vector control
Speed control
⎯
⎯
9999
(
Pr. 451
initial
value)
V/F control, advanced magnetic flux vector control
9999
⎯
*
V/F control