Limit the output frequency
4
P
ARAME
T
E
R
S
4.9 Limit the output frequency
4.9.1
Maximum/minimum frequency (Pr. 1, Pr. 2, Pr. 18)
(2) Set minimum frequency
⋅
Use
Pr. 2 Minimum frequency
to set the lower limit of the output frequency.
⋅
The output frequency is clamped by the
Pr. 2
setting even if the set frequency is equal to or less than the
Pr. 2
setting
(The frequency will not decrease to the
Pr. 2
setting.)
Purpose
Parameter that must be Set
Refer to Page
Set upper limit and lower limit of
output frequency
Maximum/minimum
frequency
Pr. 1, Pr. 2, Pr. 18
151
Perform operation by avoiding
mechanical resonance points
Frequency jump
Pr. 31 to Pr. 36
152
You can limit the motor speed. Clamp the upper and lower limits of the output frequency.
Parameter
Number
Name
Initial Value
Setting Range
Description
1
Maximum frequency
01800 or less
120Hz
0 to 120Hz
Set the upper limit of the output
frequency.
02160 or more
60Hz
2
Minimum frequency
0Hz
0 to 120Hz
Set the lower limit of the output
frequency.
18
High speed maximum
frequency
01800 or less
120Hz
120 to 400Hz
Set when performing the
operation at 120Hz or more.
02160 or more
60Hz
(1) Set maximum frequency
⋅
Set the upper limit of the output frequency in
Pr. 1 Maximum
frequency
. If the frequency of the frequency command entered is
higher than the setting, the output frequency is clamped at the
maximum frequency.
⋅
When you want to perform operation above 120Hz, set the upper
limit of the output frequency to
Pr. 18 High speed maximum
frequency
. (When
Pr. 18
is set,
Pr. 1
automatically switches to the
frequency of
Pr. 18
. When
Pr. 18
is set,
Pr. 18
automatically
switches to the frequency of
Pr. 1
.)
REMARKS
⋅
When performing operation above 50Hz using the frequency setting analog signal, change
Pr. 125 (Pr. 126) (frequency setting
gain)
. If only
Pr. 1
or
Pr. 18
is changed, operation above 60Hz cannot be performed.
REMARKS
⋅
When
Pr. 15 Jog frequency
is equal to or less than
Pr. 2
, the
Pr. 15
setting has precedence over the
Pr. 2
setting.
⋅
When stall prevention is activated to decrease the output frequency, the output frequency may drop to
Pr. 2
or below.
CAUTION
Note that when
Pr. 2
is set to any value equal to or more than
Pr. 13 Starting frequency
, simply turning on the start
signal will run the motor at the preset frequency according to the set acceleration time even if the command
frequency is not input.
♦
Parameters referred to
♦
Pr. 13 Starting frequency
Refer to page 169
Pr. 15 Jog frequency
Refer to page 162
Pr. 125 Terminal 2 frequency setting gain frequency, Pr. 126 Terminal 4 frequency setting gain frequency
Refer to page 282
Output frequency
(Hz)
Pr.1
Pr.18
Pr.2
Frequency setting
Clamped at the
maximum frequency
Clamped at the
minimum frequency
5, 10V
(20mA)
0
(4mA)