162
Frequency setting by external terminals
4.11.2 Jog operation (Pr. 15, Pr. 16)
The above parameters are displayed as simple mode parameters only when the parameter unit (FR-PU04/FR-PU07) is connected. When the
operation panel (FR-DU07) is connected, the above parameters can be set only when
Pr. 160 User group read selection
= "0".
(Refer to page 299)
* When the setting of
Pr. 21 Acceleration/deceleration time increments
is "0" (initial value), the setting range is "0 to 3600s" and the setting increments are
"0.1s", and when the setting is "1", the setting range is "0 to 360s" and the setting increments are "0.01s"
(1) Jog operation from outside
⋅
When the jog signal is on, a start and stop can be made by the start signal (STF, STR). (The jog signal is assigned
to the terminal JOG in the initial setting)
You can set the frequency and acceleration/deceleration time for jog operation. Jog operation can be performed
from either the outside or PU.
Can be used for conveyor positioning, test operation, etc.
Parameter
Number
Name
Initial
Value
Setting Range
Description
15
Jog frequency
5Hz
0 to 400Hz
Set the frequency for jog operation.
16
Jog
acceleration/
deceleration
time
0.5s
0 to 3600/360s*
Set the acceleration/deceleration time for jog operation. Set the
time taken to reach the frequency (Initial value is 50Hz) set in
Pr. 20
Acceleration/deceleration reference frequency
for acceleration/
deceleration time.
The acceleration and deceleration time cannot be set separately.
REMARKS
⋅
When you want to change the running frequency, change
Pr. 15 Jog frequency
. (initial value "5Hz")
⋅
When you want to change the acceleration/deceleration time change
Pr. 16 Jog acceleration/deceleration time
. (initial value
"0.5s")
Output
frequency(Hz)
Pr.20
Pr.15
Jog frequency
setting range
Pr.16
Forward
rotation
Reverse
rotation
Time
ON
ON
ON
JOG signal
Forward
rotation STF
Reverse
rotation STR
STF
10
2
5
JOG
Motor
Inverter
R/L
1
S/L
2
T/L
3
U
V
W
Connection diagram for external jog operation
STR
Three-phase AC
power supply
Forward rotation start
Reverse rotation start
JOG signal
PC
1.
Screen at powering on
Confirm that the external operation mode is selected.
([EXT] lit)
If not displayed, press to change to the
external [EXT] operation mode.
If the operation mode still does not change,
set Pr. 79 to change to the external operation mode.
Indication
Operation
2.
Turn the JOG switch on.
ON
Forward
rotation
Forward
rotation
Reverse
rotation
Reverse
rotation
Rotates while ON
Stop
3.
Turn the start switch (STF or STR) on.
The motor rotates while start switch
(STF or STR) is ON.
Rotates at 5Hz. (Initial value of
Pr. 15
)
4.
Turn the start switch (STF or STR) off.
ON
OFF