78
Param
e
te
r List
Parameter List
E
n
ergy savi
ng moni
to
r
891
Cumulative power monitor digit shifted
times
0 to 4, 9999
1
9999
267
892
Load factor
30 to 150%
0.1%
100%
267
893
Energy saving monitor reference
(motor capacity)
0.1 to 55/0 to 3600kW
*2
0.01/
0.1kW
*2
Inverter
rated
capacity
267
894
Control selection during commercial
power-supply operation
0, 1, 2, 3
1
0
267
895
Power saving rate reference value
0, 1, 9999
1
9999
267
896
Power unit cost
0 to 500, 9999
0.01
9999
267
897
Power saving monitor average time
0, 1 to 1000h, 9999
1
9999
267
898
Power saving cumulative monitor clear
0, 1, 10, 9999
1
9999
267
899
Operation time rate (estimated value)
0 to 100%, 9999
0.1%
9999
267
Calibrat
ion p
aram
et
er
s
C0
(900)
CA terminal calibration
⎯
⎯
⎯
251
C1
(901)
AM terminal calibration
⎯
⎯
⎯
251
C2
(902)
Terminal 2 frequency setting bias
frequency
0 to 400Hz
0.01Hz
0Hz
282
C3
(902)
Terminal 2 frequency setting bias
0 to 300%
0.1%
0%
282
125
(903)
Terminal 2 frequency setting gain
frequency
0 to 400Hz
0.01Hz
50
Hz
282
C4
(903)
Terminal 2 frequency setting gain
0 to 300%
0.1%
100%
282
C5
(904)
Terminal 4 frequency setting bias
frequency
0 to 400Hz
0.01Hz
0Hz
282
C6
(904)
Terminal 4 frequency setting bias
0 to 300%
0.1%
20%
282
126
(905)
Terminal 4 frequency setting gain
frequency
0 to 400Hz
0.01Hz
50
Hz
282
C7
(905)
Terminal 4 frequency setting gain
0 to 300%
0.1%
100%
282
A
nalog out
put
cu
rrent
calibrat
ion
C8
(930)
Current output bias signal
0 to 100%
0.1%
0%
251
C9
(930)
Current output bias current
0 to 100%
0.1%
0%
251
C10
(931)
Current output gain signal
0 to 100%
0.1%
100%
251
C11
(931)
Current output gain current
0 to 100%
0.1%
100%
251
Calibrat
ion p
a
ram
e
te
rs
C12
(917)
Terminal 1 bias frequency (speed)
0 to 400Hz
0.01Hz
0Hz
282
C13
(917)
Terminal 1 bias (speed)
0 to 300%
0.1%
0%
282
C14
(918)
Terminal 1 gain frequency (speed)
0 to 400Hz
0.01Hz
50
Hz
282
C15
(918)
Terminal 1 gain (speed)
0 to 300%
0.1%
100%
282
C16
(919)
Terminal 1 bias command (torque/
magnetic flux)
0 to 400%
0.1%
0%
288
C17
(919)
Terminal 1 bias (torque/magnetic flux)
0 to 300%
0.1%
0%
288
C18
(920)
Terminal 1 gain command (torque/
magnetic flux)
0 to 400%
0.1%
150%
288
C19
(920)
Terminal 1 gain (torque/magnetic flux)
0 to 300%
0.1%
100%
288
C38
(932)
Terminal 4 bias command (torque/
magnetic flux)
0 to 400%
0.1%
0%
288
C39
(932)
Terminal 4 bias (torque/magnetic flux)
0 to 300%
0.1%
20%
288
C40
(933)
Terminal 4 gain command (torque/
magnetic flux)
0 to 400%
0.1%
150%
288
C41
(933)
Terminal 4 gain (torque/magnetic flux)
0 to 300%
0.1%
100%
288
⎯
989
Parameter copy alarm release
10, 100
1
10/100
*2
386
PU
990
PU buzzer control
0, 1
1
1
383
991
PU contrast adjustment
0 to 63
1
58
383
Func-
tion
Parameter
Name
Setting Range
Minimum
Setting
Increments
Initial Value
Refer
to
Page
Customer
Setting
Содержание FR-A740-00023-EC
Страница 58: ...48 MEMO...
Страница 70: ...60 MEMO...
Страница 400: ...390 MEMO...
Страница 450: ...440 MEMO...
Страница 473: ...463 MEMO...