Function assignment of external terminal and control
90
190
Y90
Life alarm
Output when any of the control circuit
capacitor, main circuit capacitor and inrush
current limit circuit or the cooling fan
approaches the end of its service life.
Pr. 255 to Pr. 259
374
91
191
Y91
Alarm output 3
(power-off signal)
Output when an error occurs due to the circuit
failure or connection alarm of the inverter.
⎯
236
92
192
Y92
Energy saving
average value
updated timing
Turned on and off alternately every time the
power saving average value is updated when
the power saving monitor is used.
Cannot be set to
Pr. 195
and
Pr. 196
(relay
output terminal).
Pr. 52, Pr. 54,
Pr. 158, Pr. 891 to
Pr. 899
267
93
193
Y93
Current average value
monitor signal
Average current value and maintenance timer
value are output as pulses.
Cannot be set to
Pr. 195
and
Pr. 196
(relay
output terminal).
Pr. 555 to Pr. 557
378
94
194
ALM2 Alarm output 2
Output when the inverter protective function
is activated to stop the output (major fault).
Continue outputting the signal during inverter
reset and stop outputting after reset is
cancelled.
*2
⎯
236
95
195
Y95
Maintenance timer
signal
Output when
Pr. 503
rises to or above the
Pr.
504
setting.
Pr. 503, Pr. 504
377
96
196
REM
Remote output
Output to the terminal when a value is set to
the parameter.
Pr. 495 to Pr. 497
241
97
197
ER
Minor fault output 2
When
Pr. 875
= "0" (initial value), the signal is
output when the inverter protective function is
activated to stop the output (major fault).
When
Pr. 875
= "1", the signal is output when
the inverter protective function is activated at
occurrence of OHT/THM/PTC error and
deceleration is started.
Output when other protective functions are
activated to stop output.
Pr. 875
265
98
198
LF
Minor fault output
Output when a minor fault (fan failure or
communication error warning) occurs.
Pr. 121, Pr. 244
320, 373
99
199
ALM
Alarm output
Output when the inverter protective function is
activated to stop the output (major fault). The
signal output is stopped when a reset turns on.
⎯
236
9999
⎯
No function
⎯
⎯
⎯
*1
Note that when the frequency setting is varied using an analog signal or
of the operation panel (FR-DU07), the output of the SU (up to
frequency) signal may alternate on and off depending on that varying speed and the timing of the varying speed due to acceleration/deceleration
time setting. (The output will not alternate on and off when the acceleration/deceleration time setting is "0s".)
*2
When a power supply reset is performed, the alarm output 2 signal (ALM2) turns off as soon as the power supply switches off.
*3
Up to frequency SU, frequency detection FU, FU2, FU3 under encoder feed back control or vector control (option FR-A7AP is mounted) signals
are as below.
SU, FU: Output when the actual speed (frequency) by the encoder feedback signal exceeds detected specification frequency.
FU2, FU3: Output when the inverter output frequency exceeds detected specification frequency.
*4
This function is valid when the FR-A7AP (option) is mounted.
REMARKS
⋅
The same function may be set to more than one terminal.
⋅
When the function is executed, the terminal conducts at the setting of any of "0" to "99", and does not conduct at the setting of
any of "100" to "199".
⋅
The signal will not function if a value other than the above is set to any of
Pr. 190 to Pr. 196
.
⋅
When
Pr. 76 Alarm code output selection
= "1", the output signals of the terminals SU, IPF, OL and FU are switched as set in
Pr.
76
. (When an inverter alarm occurs, the signal output is switched to the alarm output.)
⋅
The output assignment of the terminal RUN and alarm output relay are as set above regardless of
Pr. 76
.
CAUTION
⋅
When terminal assignment is changed using
Pr. 190 to Pr. 196 (output terminal function selection)
, the other functions may be
affected. Please make setting after confirming the function of each terminal.
⋅
Do not assign signals which repeat frequent ON/OFF to A1, B1, C1, A2, B2, C2. Otherwise, the life of the relay contact
decreases.
Setting
Signal
Name
Function
Operation
Related
Parameters
Refer to
Page
Positive
Logic
Negative
Logic