352
Special operation and frequency control
(4) I/O signals and parameter setting
⋅
Turn on the X14 signal to perform PID control. When this signal is off, PID action is not performed and normal
inverter operation is performed. (Note that it is not necessary to turn on X14 signal when performing PID control
with using LONWORKS or CC-Link communication. )
⋅
Enter the set point across inverter terminals 2-5 or into
Pr. 133
and enter the measured value signal across inverter
terminals 4-5. At this time, set "20" or "21" in
Pr. 128
.
⋅
When entering the externally calculated deviation signal, enter it across terminals 1-5. At this time, set "10" or "11"
in
Pr. 128
.
Signal
Terminal
Used
Function
Description
Parameter Setting
In
put
X14
Depending on
Pr. 178 to Pr.
189
PID control selection Turn on X14 to perform PID control.
Set 14 in any of
Pr. 178 to Pr. 189
.
X64
PID forward/
reverse action
switchover
By turning on X64, forward action can be
selected for PID reverse action (
Pr. 128
=
10, 20), and reverse action for forward
action (
Pr. 128
= 11, 21).
Set 64 in any of
Pr. 178 to Pr. 189
.
2
2
Set point input
Enter the set point for PID control.
Pr. 128
= 20, 21,
Pr. 133
= 9999
0 to 5V................0 to 100%
Pr. 73
= 1
*1
, 3, 5, 11, 13, 15
0 to 10V..............0 to 100%
Pr. 73
= 0, 2, 4, 10, 12, 14
0 to 20mA...........0 to 100%
Pr. 73
= 6, 7, 16, 17
PU
⎯
Set point input
Set the set value
(Pr. 133)
from the
operation panel or parameter unit.
Pr. 128
= 20, 21,
Pr. 133
= 0 to 100%
1
1
Deviation signal
input
Input the deviation signal calculated
externally.
Pr. 128
= 10
*1
, 11
-5V to +5V ..........-100% to +100%
Pr. 73
= 2, 3, 5, 7, 12, 13, 15, 17
-10V to +10V ......-100% to +100%
Pr. 73
= 0, 1
*1
, 4, 6, 10, 11, 14, 16
4
4
Measured value
input
Input the signal from the detector
(measured value signal).
Pr. 128
= 20, 21
4 to 20mA. 0 to 100%
Pr. 267
= 0
*1
0 to 5V...... 0 to 100%
Pr. 267
= 1
0 to 10V.... 0 to 100%
Pr. 267
= 2
Communi-
cation
*2
⎯
Deviation value
input
Input the deviation value from
L
ON
W
ORKS
, CC-Link communication.
Pr. 128
= 50, 51
Set value, measured
value input
Input the set value and measured value
from L
ON
W
ORKS
, CC-Link communication.
Pr. 128
= 60, 61
PLC
⎯
Deviation value
input
Input the deviation value from PLC
function.
Pr. 128
= 70, 71, 90, 91
Set value, measured
value input
Input the set value and measured value
from PLC function.
Pr. 128
= 80, 81, 100, 101
Ou
tp
u
t
FUP
Depending on
Pr. 190 to Pr.
196
Upper limit output
Output to indicate that the measured
value signal exceeded the maximum
value
(Pr. 131)
.
Pr. 128
= 20, 21, 60, 61
Pr. 131
≠
9999
Set 15 or 115 in any of
Pr. 190 to Pr. 196
.
*3
FDN
Lower limit output
Output when the measured value signal
falls below the minimum value
(Pr. 132)
.
Pr. 128
= 20, 21, 60, 61
Pr. 132
≠
9999
Set 14 or 114 in any of
Pr. 190 to Pr. 196
.
*3
RL
Forward (reverse)
rotation direction
output
"Hi" is output to indicate that the output
indication of the parameter unit is forward
rotation (FWD) or "Low" to indicate that it
is reverse rotation (REV) or stop (STOP).
Set 16 or 116 in any of
Pr. 190 to Pr.
196
.
*3
PID
During PID
control activated
Turns on during PID control.
Set 47 or 147 in any of
Pr. 190 to Pr.
196
.
*3
SLEEP
PID output
interruption
Turns on when the PID output
interruption function is performed.
Pr. 575
≠
9999
Set 70 or 170 in any of
Pr. 190 to Pr.
196
.
*3
SE
SE
Output terminal
common
Common terminal for terminals FUP,
FDN, RL, PID and SLEEP
*1
The shaded area indicates the parameter initial value.
*2
For the setting method via L
ON
W
ORKS
communication, refer to the L
ON
W
ORKS
communication option (FR-A7NL) instruction manual.
For the setting method via CC-Link communication, refer to the CC-Link communication option (FR-A7NC) instruction manual.
*3
When 100 or larger value is set in any of
Pr. 190 to Pr. 196 (output terminal function selection)
, the terminal output has negative logic.
(Refer to
page 230 for details)
CAUTION
⋅
Changing the terminal function using any of
Pr. 178 to Pr. 189, 190 to Pr. 196
may affect the other functions. Please make setting
after confirming the function of each terminal.
⋅
When the
Pr. 73
and
Pr. 267
settings were changed, check the voltage/current input switch setting. Different setting may cause a
fault, failure or malfunction. (
Refer to page 275
for setting.)