Param
e
te
r List
Parameter List
P
ID operat
ion
127
PID control automatic switchover
frequency
0 to 400Hz, 9999
0.01Hz
9999
348
128
PID action selection
10, 11, 20, 21, 50, 51, 60,
61, 70, 71, 80, 81, 90, 91,
100, 101
1
10
348
129
PID proportional band
0.1 to 1000%, 9999
0.1%
100%
348
130
PID integral time
0.1 to 3600s, 9999
0.1s
1s
348
131
PID upper limit
0 to 100%, 9999
0.1%
9999
348
132
PID lower limit
0 to 100%, 9999
0.1%
9999
348
133
PID action set point
0 to 100%, 9999
0.01%
9999
348
134
PID differential time
0.01 to 10.00s, 9999
0.01s
9999
348
Elect
ronic byp
a
ss
135
Electronic bypass sequence selection
0, 1
1
0
356
136
MC switchover interlock time
0 to 100s
0.1s
1s
356
137
Start waiting time
0 to 100s
0.1s
0.5s
356
138
Bypass selection at an alarm
0, 1
1
0
356
139
Automatic switchover frequency from
inverter to bypass operation
0 to 60Hz, 9999
0.01Hz
9999
356
Bac
kl
a
sh
meas
ures
140
Backlash acceleration stopping
frequency
0 to 400Hz
0.01Hz
1Hz
170
141
Backlash acceleration stopping time
0 to 360s
0.1s
0.5s
170
142
Backlash deceleration stopping
frequency
0 to 400Hz
0.01Hz
1Hz
170
143
Backlash deceleration stopping time
0 to 360s
0.1s
0.5s
170
⎯
144
Speed setting switchover
0, 2, 4, 6, 8, 10, 102,
104, 106, 108, 110
1
4
242
PU
145
PU display language selection
0 to 7
1
1
381
Current d
e
te
ct
ion
148
Stall prevention level at 0V input
0 to 220%
0.1%
150%
144
149
Stall prevention level at 10V input
0 to 220%
0.1%
200%
144
150
Output current detection level
0 to 220%
0.1%
150%
239
151
Output current detection signal delay
time
0 to 10s
0.1s
0s
239
152
Zero current detection level
0 to 220%
0.1%
5%
239
153
Zero current detection time
0 to 1s
0.01s
0.5s
239
⎯
154
Voltage reduction selection during stall
prevention operation
0, 1
1
1
144
⎯
155
RT signal function validity condition
selection
0, 10
1
0
226
⎯
156
Stall prevention operation selection
0 to 31, 100, 101
1
0
144
⎯
157
OL signal output timer
0 to 25s, 9999
0.1s
0s
144
⎯
158
AM terminal function selection
1 to 3, 5 to 14, 17, 18,
21, 24, 32 to 34, 50,
52, 53, 70
1
1
244
⎯
159
Automatic switchover frequency range
from bypass to inverter operation
0 to 10Hz, 9999
0.01Hz
9999
356
⎯
160
User group read selection
0, 1, 9999
1
0
299
⎯
161
Frequency setting/key lock operation
selection
0, 1, 10, 11
1
0
381
A
u
to
mat
ic
res
tar
t
funct
ions
162
Automatic restart after instantaneous
power failure selection
0, 1, 2, 10, 11, 12
1
0
254
163
First cushion time for restart
0 to 20s
0.1s
0s
254
164
First cushion voltage for restart
0 to 100%
0.1%
0%
254
165
Stall prevention operation level for
restart
0 to 220%
0.1%
150%
254
Curr
ent
det
ec
tion
166
Output current detection signal
retention time
0 to 10s, 9999
0.1s
0.1s
239
167
Output current detection operation
selection
0, 1
1
0
239
Func-
tion
Parameter
Name
Setting Range
Minimum
Setting
Increments
Initial Value
Refer
to
Page
Customer
Setting
Содержание FR-A740-00023-EC
Страница 58: ...48 MEMO...
Страница 70: ...60 MEMO...
Страница 400: ...390 MEMO...
Страница 450: ...440 MEMO...
Страница 473: ...463 MEMO...