Causes and corrective actions
Operation Panel
Indication
E.11
FR-PU04
FR-PU07
Fault 11
Name
Opposite rotation deceleration error
Description
The speed may not decelerate during low speed operation if the rotation direction of the speed
command and the estimated speed differ when the rotation is changing from forward to reverse or from
reverse to forward during torque control under real sensorless vector control. At this time, the inverter
output is stopped if the rotation direction will not change, causing overload.
Check point
Check that the rotation direction is not switched from forward to reverse rotation (or from reverse to
forward) during torque control under real sensorless vector control.
Corrective action
· Prevent the motor from switching the rotation direction from forward to reverse (or from reverse to
forward) during torque control under real sensorless vector control.
· Please contact your sales representative.
Operation Panel
Indication
E.13
FR-PU04
FR-PU07
Fault 13
Name
Internal circuit error
Description
Appears when an internal circuit error occurred.
Corrective action
Please contact your sales representative.
CAUTION
• If protective functions of E.ILF, E.PTC, E.PE2, E.EP, E.OD, E.CDO, E.IOH, E.SER, E.AIE, E.USB are activated when using the
FR-PU04, "Fault 14" appears.
Also when the alarm history is checked on the FR-PU04, the display is "E.14".
• If alarms other than the above appear, contact your sales representative.