237
Function assignment of external terminal and control
4
P
ARAME
T
E
R
S
4.15.7 Detection of output frequency (SU, FU, FU2 , FU3, FB, FB2, FB3, LS signal,
Pr. 41 to Pr. 43, Pr. 50, Pr. 116, Pr. 865)
The inverter output frequency is detected and output to the output signal.
Parameter
Number
Name
Initial
Value
Setting
Range
Description
41
Up-to-frequency sensitivity
10%
0 to 100%
Set the level where the SU signal turns on.
42
Output frequency detection
6Hz
0 to 400Hz
Set the frequency where the FU (FB) signal turns on.
43
Output frequency detection
for reverse rotation
9999
0 to 400Hz
Set the frequency where the FU (FB) signal turns on
in reverse rotation.
9999
Same as
Pr. 42
setting
50
Second output frequency
detection
30Hz
0 to 400Hz
Set the frequency where the FU2 (FB2) signal turns
on.
116
Third output frequency
detection
50Hz
0 to 400Hz
Set the frequency where the FU3 (FB3) signal turns
on.
865
Low speed detection
1.5Hz
0 to 400Hz
Set the frequency where the LS signal turns on.
(1) Up-to-frequency sensitivity (SU signal,
Pr. 41
)
⋅
When the output frequency reaches the set frequency, the up-to-frequency
signal (SU) is output.
⋅
The
Pr. 41
value can be adjusted within the range
±
1% to
±
100% on the
assumption that the set frequency is 100%.
⋅
This parameter can be used to ensure that the set frequency has been
reached to provide the operation start signal etc. for related equipment.
(2) Output frequency detection (FU (FB) signal, FU2 (FB2) signal, FU3 (FB3) signal,
Pr. 42, Pr. 43,
Pr. 50, Pr. 116
)
⋅
When the output frequency rises to or above the
Pr. 42
setting, the output frequency detection signal (FU, FB) is
output.
⋅
This function can be used for electromagnetic brake operation, open signal, etc.
⋅
The FU (FU2, FU3) signal is output when the output frequency reaches the set frequency. While the FB (FB2, FB3)
signal is output when the actual rotation detection speed (during real sensorless vector control : speed estimated
value, during vector control : feedback value) of the motor reaches the set frequency. The FU signal and FB signal
are output simultaneously during V/F control and advanced magnetic flux vector control.
⋅
When the detection frequency is set in
Pr. 43
, frequency detection used exclusively for reverse rotation can also be
set. This function is effective for switching the timing of electromagnetic brake operation between forward rotation
(rise) and reverse rotation (fall) during elevator operation, etc.
⋅
When
Pr. 43
≠
"9999", the
Pr. 42
setting applies to forward rotation and the
Pr. 43
setting applies to reverse rotation.
⋅
When outputting a frequency detection signal besides the FU signal, set the detection frequency in
Pr. 50 or Pr. 116
.
The FU2 (FB2) signal (FU3(FB3) signal if
Pr. 116
or more) is output when the output frequency reaches or exceeds
the
Pr. 50
setting.
⋅
For each signal, assign functions to
Pr. 190 to Pr. 196 (output terminal function selection)
referring to the table below.
Output frequency
(Hz)
ON
Set frequency
Adjustment
range
Pr.41
SU
Time
OFF
OFF
Forward
rotation
Pr.116
Pr.50
Pr.42
Pr.43
Pr.50
Pr.116
OFF
ON
OFF
ON
OFF
Time
(Hz)
FU/FB
FU2/FB2
FU3/FB3
Output
signal
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
Output frequecy
Reverse
rotation
Parameter
Number
Output
Signal
Pr. 190 to Pr. 196
Setting
Positive
logic
Negative
logic
42, 43
FU
4
104
FB
41
141
50
FU2
5
105
FB2
42
142
116
FU3
6
106
FB3
43
143