291
Frequency/torque setting by analog
input (terminal 1, 2, 4)
4
P
ARAME
T
E
R
S
b) Method to adjust any point without application of a voltage (current) to across terminals 1-5(4-5)
(To change from 8V (80%) to 10V (100%))
REMARKS
You can check the current torque setting bias/gain setting by pressing
after step 6.
You can not check after performing operation in step 7.
1.
Confirmation of the RUN indication and
operation mode indication
The inverter must be at a stop.
The inverter must be in the PU operation
mode. (Using )
Display
Operation
Analog voltage (current)
value (%) across terminals 1-5
(across terminals 4-5)
The gain torque is
reached when the analog
voltage (current) value across
terminals 1-5 (across terminals
4-5) is 100%.
Flicker...Parameter setting complete!!
(Adjustment completed)
C0
to
C41
setting
is enabled.
Terminal 1 input
Terminal 4 input
Terminal 1 input Terminal 4 input
The parameter
number read
previously appears.
2.
Press to choose the parameter
setting mode.
3.
Turn until appears.
4.
Press to display .
5.
Turn until ( )
appears. Set to
C19 Terminal 1 gain (torque)
.
6.
Press to display the analog voltage
(current) value (%).
7.
Turn to set the gain voltage (%).
"0V (0mA) equals to 0%, 10V (5V,
20mA) to 100%"
8.
Press to set.
REMARKS
The current setting at the instant of turning
is displayed.
By turning , you can read another parameter.
Press to return to the indication (step 4).
Press twice to show the next parameter ( ).
Содержание FR-A740-00023-EC
Страница 58: ...48 MEMO...
Страница 70: ...60 MEMO...
Страница 400: ...390 MEMO...
Страница 450: ...440 MEMO...
Страница 473: ...463 MEMO...