![Mitsubishi FR-A740-00023-EC Скачать руководство пользователя страница 204](http://html1.mh-extra.com/html/mitsubishi/fr-a740-00023-ec/fr-a740-00023-ec_instruction-manual_1809251204.webp)
194
Motor brake and stop operation
4.14 Motor brake and stop operation
4.14.1 DC injection brake and zero speed control, servo lock (LX signal, X13 signal,
Pr. 10 to Pr. 12, Pr. 802, Pr. 850)
* This parameter can be set when the FR-A7AP (option) is mounted.
Purpose
Parameter that must be Set
Refer to Page
Motor braking torque adjustment
DC injection brake and zero speed
control, servo lock
Pr. 10 to Pr. 12,
Pr. 802, Pr. 850
194
Improve the motor braking torque
with an option
Selection of a regenerative brake
Pr. 30, Pr. 70
198
Performing operation by DC current
input
DC current feeding mode
Pr. 30
198
Coast the motor to a stop
Selection of motor stopping method
Pr. 250
204
Used to stop the motor with a
mechanical brake (vibration restraint
at stop-on-contact)
Stop-on-contact control
Pr. 270, Pr. 275,
Pr. 276
205
Used to stop the motor with a
mechanical brake (operation timing
of a mechanical brake)
Brake sequence function
Pr. 278 to Pr. 285,
Pr. 292
208
Perform position stop (orientation)
control of the rotation shaft
Orientation control
Pr. 350 to Pr. 366,
Pr. 369, Pr. 393,
Pr. 396 to Pr. 399
211
The DC injection brake can be operated at a motor stop to adjust the stop timing and braking torque.
Zero speed control can be selected during real sensorless vector control and either zero speed control or servo
lock can be selected under vector control.
In DC injection brake operation, DC voltage is directly applied to the motor to prevent the motor shaft from
rotating when a motor decelerates to stop. While, in zero speed control, vector control is performed to maintain
0r/min. In either control, the motor will not return to the original position if the motor shaft rotates due to external
force.
The motor shaft position is maintained with servo lock. The motor will return to the original position if the motor
shaft rotates due to external force.
Parameter
Number
Name
Initial Value
Setting Range
Description
10
DC injection brake
operation frequency
3Hz
0 to 120Hz
Set the operation frequency of the DC
injection brake (zero speed control, servo
lock).
9999
Operated at
Pr. 13
or less.
11
DC injection brake
operation time
0.5s
0
DC injection brake (zero speed control)
disabled
0.1 to 10s
Set the operation time of the DC injection
brake (zero speed control, servo lock).
8888
Operate when X13 signal is on
12
DC injection brake
operation voltage
00250 or less
4%
0 to 30%
Set the DC injection brake voltage (torque).
When "0" is set, DC injection brake is disabled.
00310 to 01800 2%
02160 or more
1%
802 *
Pre-excitation
selection
0
0
Zero speed control
1
Servo lock
850
Brake operation
selection
0
0
DC injection brake operation
1
Zero speed control
Содержание FR-A740-00023-EC
Страница 58: ...48 MEMO...
Страница 70: ...60 MEMO...
Страница 400: ...390 MEMO...
Страница 450: ...440 MEMO...
Страница 473: ...463 MEMO...