206
Motor brake and stop operation
(1) Set stop-on-contact control
⋅
Make sure that the inverter is in external operation mode.
(Refer to page 301 )
⋅
Select either real sensorless vector control or advanced magnetic flux vector control.
⋅
Set"1 or 3" in
Pr. 270
Stop-on contact/load torque high-speed frequency control selection
.
⋅
Set output frequency during stop-on-contact control in
Pr. 6
Multi-speed setting (low speed)
.
The frequency should be as low as possible (about 2Hz). If it is set to more than 30Hz, the operating frequency will
be 30Hz.
⋅
When both the RT and RL signals are switched on, the inverter enters the stop-on-contact mode, in which operation
is performed at the frequency set in
Pr. 6
independently of the preceding speed.
(2) Function switching of stop-on-contact control selection
* When RL and RT are on,
Pr. 49 Second stall prevention operation frequency
is invalid.
CAUTION
⋅
By increasing the
Pr. 275
setting, the low-speed (stop-on-contact) torque increases, but overcurrent alarm (E.OCT) may occur or
the machine may oscillate in a stop-on-contact state.
⋅
The stop-on-contact function is diferent from servo-lock function, and if used to stop or hold a load for an extended period, this
function can cause the motor to overheat.
After a stop, immediately reset this function and use a mechanical brake to hold the load.
⋅
Under the following operating conditions, the stop-on-contact function is made invalid:
PU operation
(Pr. 79)
·
JOG operation (JOG signal)
·
PU+external operation
(Pr. 79)
·
PID control function operation
(Pr. 128)
·
Remote setting function operation
(Pr. 59)
·
Start time tuning
·
Orientation control function operation
⋅
When performing stop-on-contact control during encoder feedback control, encoder feedback control is made invalid due to a
mode shift to the stop-on-contact control mode.
Useful Functions
Normal Operation
(either RL or RT is off or both are off)
With Stop-on-Contact Control
(both RL and RT are on)
Real sensorless
vector control
Advanced
magnetic flux vector
control
Real sensorless
vector control
Advanced
magnetic flux vector
control
Output frequency
Multi-speed
0 to 5V, 0 to 10V
4 to 20mA etc.
Pr. 6
setting
Stall prevention operation level
⎯
Pr. 22
setting
⎯
The smaller value set
in either
Pr. 22
or
Pr. 48
.
*
Torque limit level
Pr. 22
setting
⎯
Pr. 22
setting
⎯
Excitation current low speed
scaling factor
⎯
⎯
The current is
compensated for by
Pr.
275
(0 to 1000%)
settings before RL and
RT are switched on.
Carrier frequency
Pr. 72
setting
Pr. 276
setting when output frequency is 3Hz or
less (
Pr. 72
when
Pr. 276
= "9999")
Fast response current limit
⎯
Valid
⎯
Invalid