341
Communication operation and setting
4
P
ARAME
T
E
R
S
(6) Modbus registers
System environment variable
*1
The communication parameter values are not cleared.
*2
For write, set the data as a control input instruction. For read, data is read as an inverter operating status.
*3
For write, set data as the operation mode setting. For read, data is read as the operation mode status.
Register
Definition
Read/Write
Remarks
40002
Inverter reset
Write
Any value can be written
40003
Parameter clear
Write
Set H965A as a written value.
40004
All parameter clear
Write
Set H99AA as a written value.
40006
Parameter clear
*1
Write
Set H5A96 as a written value.
40007
All parameter clear
*1
Write
Set HAA99 as a written value.
40009
Inverter status/control input instruction
*2
Read/write
See below.
40010
Operation mode/inverter setting
*3
Read/write
See below.
40014
Running frequency (RAM value)
Read/write
According to the
Pr. 37
and
Pr. 144
settings, the
frequency and selectable speed are in 1r/min
increments.
40015
Running frequency (EEPROM value)
Write
<Inverter status/control input instruction>
*1
The signal within parentheses is the initial setting. The description changes depending on the setting of
Pr. 180 to Pr. 189 (input
terminal function selection) (page 222)
.
Each assigned signal is valid or invalid depending on NET.
(Refer to page 310)
*2
The signal within parentheses is the initial setting. The description changes depending on the setting of
Pr. 190 to Pr. 196 (output
terminal function selection) (page 230)
.
Bit
Definition
Control input instruction
Inverter status
0
Stop command
RUN (inverter running)
*2
1
Forward rotation command
Forward rotation
2
Reverse rotation command
Reverse rotation
3
RH (high speed operation command)
*1
SU (up to frequency)
*2
4
RM (middle speed operation command)
*1
OL (overload)
*2
5
RL (low speed operation command)
*1
IPF (instantaneous power failure)
*2
6
JOG (Jog operation)
*1
FU (frequency detection)
*2
7
RT (second function selection)
*1
ABC1 (alarm)
*2
8
AU (current input selection)
*1
ABC2 (
⎯
)
*2
9
CS
(selection of automatic restart after
instantaneous power failure)
*1
0
10
MRS (output stop)
*1
0
11
STOP (start self-holding)
*1
0
12
RES (reset)
*1
0
13
0
0
14
0
0
15
0
Alarm occurrence
<Operation mode/inverter setting>
The restrictions depending on the
operation mode changes according
to the computer link specifications.
Mode
Read
Value
Written
Value
EXT
H0000
H0010
PU
H0001
⎯
EXT
JOG
H0002
⎯
PU
JOG
H0003
⎯
NET
H0004
H0014
PU+
EXT
H0005
⎯