137
Adjustment of real sensorless vector
control, vector control
4
P
ARAME
T
E
R
S
4.7.2
Excitation ratio (Pr. 854)
Decrease the excitation ratio when you want to improve efficiency under light load. (Motor magnetic noise
decreases.)
Parameter
Number
Name
Initial Value
Setting Range
Description
854
Excitation ratio
100%
0 to 100%
Set the excitation ratio under no load.
⋅
Note that the rise of output torque becomes slow if
excitation ratio is decreased.
This function is appropriate for applications as machine
tools which repeat rapid acceleration/deceleration up to
high speed.
REMARKS
⋅
When "1" (magnetic flux with terminal) is set in
Pr. 858 Terminal 4 function assignment
or
Pr. 868 Terminal 1 function assignment
, the
Pr. 854
setting is made invalid.
Sensorless
Sensorless
Sensorless
Sensorless
Sensorless
Sensorless
Sensorless
Sensorless
Sensorless
Vector
Vector
Vector
Excitation
ratio [%]
100
(initial value)
Pr. 854
set value
0
100
Load [%]
Содержание FR-A740-00023-EC
Страница 58: ...48 MEMO...
Страница 70: ...60 MEMO...
Страница 400: ...390 MEMO...
Страница 450: ...440 MEMO...
Страница 473: ...463 MEMO...