263
Operation setting at alarm occurrence
4
P
ARAME
T
E
R
S
4.18.2 Alarm code output selection (Pr. 76)
⋅
By setting
Pr. 76
to "1" or "2", the alarm code can be output to the output terminals.
⋅
When the setting is "2", an alarm code is output at only alarm occurrence, and during normal operation, the terminals
output the signals assigned to
Pr. 190 to Pr. 196 (output terminal function selection)
.
⋅
The following table indicates alarm codes to be output. (0: output transistor off, 1: output transistor on)
At alarm occurrence, its description can be output as a 4-bit digital signal from the open collector output
terminals.The alarm code can be read by a programmable controller, etc., and its corrective action can be shown
on a display, etc.
Parameter
Number
Name
Initial Value
Setting Range
Description
76
Alarm code output selection
0
0
Without alarm code output
1
With alarm code output
(Refer to the following table)
2
Alarm code output at alarm occurrence
only
(Refer to the following table)
Operation Panel
Indication
(FR-DU07)
Output of Output Terminals
Alarm Code
SU
IPF
OL
FU
Normal
*
0
0
0
0
0
E.OC1
0
0
0
1
1
E.OC2
0
0
1
0
2
E.OC3
0
0
1
1
3
E.OV1 to E.OV3
0
1
0
0
4
E.THM
0
1
0
1
5
E.THT
0
1
1
0
6
E.IPF
0
1
1
1
7
E.UVT
1
0
0
0
8
E.FIN
1
0
0
1
9
E. BE
1
0
1
0
A
E. GF
1
0
1
1
B
E.OHT
1
1
0
0
C
E.OLT
1
1
0
1
D
E.OPT
1
1
1
0
E
E.OP3
1
1
1
0
E
Other than the above
1
1
1
1
F
* When
Pr. 76
= "2", the output terminals output the signals assigned to
Pr. 190 to Pr. 196
.
CAUTION
⋅
When a value other than "0" is set in
Pr. 76
When an alarm occurs, the output terminals SU, IPF, OL, FU output the signal in the above table, independently of the
Pr. 190 to
Pr. 196 (output terminal function selection)
settings. Please be careful when inverter control setting has been made with the output
signals of
Pr. 190 to Pr. 196
.
♦
Parameters referred to
♦
Pr. 190 to Pr. 196 (output terminal function selection)
Refer to page 230