![Mitsubishi FR-A740-00023-EC Скачать руководство пользователя страница 103](http://html1.mh-extra.com/html/mitsubishi/fr-a740-00023-ec/fr-a740-00023-ec_instruction-manual_1809251103.webp)
4
P
ARAME
T
E
R
S
93
Speed control by real sensorless vector
control, vector control
4.4.2
Setting procedure of vector control (speed control)
CAUTION
⋅
Speed command setting range is 0 to 120Hz for vector control.
⋅
The carrier frequencies are selectable from among 2k, 6k, 10k, 14kHz for vector control.
(2k and 6kHz for the 02160 or more)
Vector
Vector
Vector
Test run
Perform secure wiring.
(Refer to page 34.)
Set the motor and encoder.
(Pr. 71, Pr. 359, Pr. 369)
Set the run command.
(Refer to page 301.)
As required
· Perform offline auto tuning.
(Pr. 96) (refer to page 181)
.
· Select online auto tuning.
(Pr. 95) (refer to page 191).
· Easy gain tuning
(refer to page 99)
· Manual input speed control gain adjustment
(refer to page 102)
Select the start command and speed command.
(1) Start command
1)Operation panel: Setting by pressing
/
of the
operation panel
2)External command: Setting by forward rotation or reverse
rotation command (terminal STF or STR)
(2)Speed command
1)Operation panel: Setting by pressing
of the operation panel
2)External analog command (terminal 2 or 4) :
Give a speed command using the analog signal input to
terminal 2 (or terminal 4).
3)Multi-speed command:
The external signals (RH, RM, RL) may also be used to give
speed command.
Set the motor capacity and the number of motor poles
(Pr. 80, Pr. 81) (Refer to page 87.)
Set the motor capacity (kW) in
Pr. 80
Motor capacity
and set the number
of motor poles (number of poles) in
Pr. 81
Number of motor poles
. (V/F
control is performed when the setting is "9999" (initial value).)
Mount the FR-A7AP.
Set
Pr. 71 Applied motor
,
Pr. 359 Encoder rotation direction
and
Pr. 369
Number of encoder pulses
according to the motor and encoder used.
(Refer to page 36.)
Select a control method.
(Refer to page 87.)
Make speed control valid by selecting "0" (speed control), "2" (speed-
torque switchover), or "4" (speed-position switchover) for
Pr. 800
.
Set the torque limit.
(Pr. 810)
(Refer to page 94.)
Содержание FR-A740-00023-EC
Страница 58: ...48 MEMO...
Страница 70: ...60 MEMO...
Страница 400: ...390 MEMO...
Страница 450: ...440 MEMO...
Страница 473: ...463 MEMO...