Special operation and frequency control
4
P
ARAME
T
E
R
S
<Set point input calibration>
1. Apply the input voltage of 0% set point setting (e.g. 0V) across terminals 2-5.
2. Enter in
C2 (Pr. 902)
the frequency which should be output by the inverter at the deviation of 0% (e.g. 0Hz).
3. In
C3 (Pr. 902)
, set the voltage value at 0%.
4. Apply the voltage of 100% set point (e.g. 5V) to across terminals 2-5.
5. Enter in
Pr. 125
the frequency which should be output by the inverter at the deviation of 100% (e.g. 50Hz).
6. In
C4 (Pr. 903)
, set the voltage value at 100%.
<Detector output calibration>
1. Apply the output current of 0% detector setting (e.g. 4mA) across terminals 4-5.
2. Make calibration using
C6 (Pr. 904)
.
3. Apply the output current of 100% detector setting (e.g. 20mA) across terminals 4-5.
4. Make calibration using
C7 (Pr. 905)
.
The results of the above calibration are as shown below:
REMARKS
⋅
The frequency set in
C5 (Pr. 904)
and
Pr. 126
should be the same as set in
C2 (Pr. 902)
and
Pr. 125
.
CAUTION
⋅
If the multi-speed (RH, RM, RL signal) or jog operation (jog signal) is entered with the X14 signal on, PID control is stopped and
multi-speed or jog operation is started.
⋅
If the setting is as follows, PID control becomes invalid.
Pr. 79
Operation mode selection
= "6" (switchover mode)
Pr. 858
Terminal 4 function assignment, Pr. 868
Terminal 1 function assignment
= "4" (torque command)
⋅
When the
Pr. 128
setting is "20" or "21", note that the input across inverter terminals 1-5 is added to the set value across terminals 2-5.
⋅
When using terminal 4 (measured value input) and terminal 1 (deviation input) under PID control, set "0" (initial value) in
Pr. 858
Terminal 4 function assignment
and "0" (initial value) in
Pr. 868
Terminal 1 function assignment
.
⋅
Changing the terminal function using any of
Pr. 178 to Pr. 189, Pr. 190 to Pr. 196
may affect the other functions. Please make
setting after confirming the function of each terminal.
⋅
When PID control is selected, the minimum frequency is the frequency set in
Pr. 902
and the maximum frequency is the
frequency set in
Pr. 903
. (
Pr. 1 Maximum frequency
and
Pr. 2 Minimum frequency
settings are also valid.)
⋅
The remote operation function is invalid during PID operation.
⋅
When the control is switched to PID control during
normal operation, the frequency command value
calculated by PID operation using 0Hz as standard is
used without the frequency during the operation.
♦
Parameters referred to
♦
Pr. 59 Remote function selection
Refer to page 164
Pr. 73 Analog input selection
Refer to page 275
Pr. 79 Operation mode selection
Refer to page 301
Pr. 178 to Pr. 189 (input terminal function selection)
Refer to page 222
Pr. 190 to Pr. 196 (output terminal function selection)
Refer to page 230
C2 (Pr. 902) to C7 (Pr. 905) Frequency setting voltage (current) bias/gain
Refer to page 282
100
0
0
5
(V)
(%)
[Set point setting]
100
0
0
20
(mA)
(%)
[Detection value]
4
0
0
100
Deviation (%)
[Manipulated variable]
Manipulated variable (Hz)
50
PID action
Frequency
command
PID set point
Frequency command
during normal operation
ON
Operation when control is switched to PID control during normal operation
Normal operation
PID operation
Normal operation