443
(5) Main differences and compatibilities with the FR-A500(L) series
Appendix 1-2 Replacement of the FR-A200 <EXCELENT> series
Instructions for installation
• When using the installation holes of the FR-A200(E) series, FR-A5AT (intercompatibility attachment) is necessary.
Item
FR-A500(L)
FR-A700
Control method
V/F control
Advanced magnetic flux vector control
V/F control
Advanced magnetic flux vector control
Real sensorless vector control
Vector control (used with a plug-in option FR-A7AP)
Changed/cleared
functions
User group 1 (16), user group 2 (16)
(Pr. 160, Pr. 173 to Pr. 175)
User group (16) only
Setting methods were partially changed
(Pr. 160, Pr. 172 to Pr. 173)
User initial value setting
(Pr. 199)
User initial value setting
(Pr. 199)
was cleared
Substitutable with the copy function of the operation
panel (FR-DU07)
Long wiring mode
(
Pr. 240
setting 10, 11)
Setting is not necessary
(
Pr. 240
settings "10" and "11" were cleared)
Intelligent mode selection
(Pr. 60)
Parameter number change
(Pr. 60 Energy saving control selection)
(Pr. 292 Automatic acceleration/deceleration)
Program operation
(Pr. 200 to Pr. 231)
Function was cleared
PID action set point setting
(Pr. 133)
Addition of "9999" to PID action set point (
Pr. 133
)
setting (a value input from terminal 2 is a set point)
Number of motor poles
(Pr. 81 , Pr. 144)
Setting the number of motor poles in Number of motor
poles (
Pr. 81
) automatically changes the speed setting
switchover (
Pr. 144
) setting.
Performing parameter clear and all clear (H5A96,
HAA99) with the FR-A7ND clears
Pr. 345
and
Pr. 346
.
Pr. 345
and
Pr. 346
are not cleared.
Terminal block
Removable terminal block
Removable terminal block
Upward compatibility (A500 terminal block mountable)
PU
FR-PU04, DU04
FR-PU07
FR-DU07
FR-PU04 (Some functions, such as parameter copy,
are unavailable.)
FR-DU04 unavailable
Plug-in options
Dedicated plug-in option (incompatible)
Computer link, relay output option
FR-A5NR
Built into the inverter
(RS-485 terminals, relay output 2 points)
Installation size
· FR-A740-00023 to 00250, 00470 to 01800, 03250, 04320 are compatible in mounting dimensions
For the FR-A740-00310, 00380, an optional intercompatibility attachment (FR-AAT) is necessary.
· Heatsink protrusion attachment is not compatible.
Also, the panel cut dimension of 00023 to 00126, 00310, 00380, 02160 or more is not compatible.
Содержание FR-A740-00023-EC
Страница 58: ...48 MEMO...
Страница 70: ...60 MEMO...
Страница 400: ...390 MEMO...
Страница 450: ...440 MEMO...
Страница 473: ...463 MEMO...