182
Selection and protection of a motor
96
Auto tuning setting/
status
0
0
Offline auto tuning is not performed
1
Offline auto tuning is performed without
motor running
101
Offline auto tuning is performed with
motor running
450
Second applied motor
9999
0 to 8, 13 to 18, 20,
23, 24, 30, 33, 34, 40, 43,
44, 50, 53, 54
Set when using the second motor.
(same specifications as
Pr. 71
)
9999
Not function
453
Second motor capacity
9999
01800 or
less
0.4 to 55kW
Set the capacity of the second motor.
02160 or
more
0 to 3600kW
9999
V/F control
454
Number of second motor
poles
9999
2, 4, 6, 8, 10
Set the number of poles of the second motor.
9999
V/F control
455
Second motor excitation
current
9999
01800 or
less
0 to 500A
Tuning data of the second motor
(The value measured by offline auto
tuning is automatically set.)
02160 or
more
0 to 3600A
9999
Use the Mitsubishi motor (SF-JR, SF-
HR, SF-JRCA, SF-HRCA, SF-V5RU)
constants
456
Rated second motor
voltage
400V
0 to 1000V
Set the rated voltage (V) of the second
motor.
457
Rated second motor
frequency
50Hz
10 to 120Hz
Set the rated motor frequency (Hz) of
the second motor.
458
Second motor constant
(R1)
9999
01800 or
less
0 to 50
Ω,
9999
Tuning data of the second motor
(The value measured by offline auto
tuning is automatically set.)
9999: Use the Mitsubishi motor (SF-JR,
SF-HR, SF-JRCA, SF-HRCA, SF-
V5RU) constants
02160 or
more
0 to 400m
Ω,
9999
459
Second motor constant
(R2)
9999
01800 or
less
0 to 50
Ω,
9999
02160 or
more
0 to 400m
Ω,
9999
460
Second motor constant
(L1)
9999
01800 or
less
0 to 50
Ω
(0 to 1000mH)
,
9999
02160 or
more
0 to 3600m
Ω
(0 to 400mH)
,
9999
461
Second motor constant
(L2)
9999
01800 or
less
0 to 50
Ω
(0 to 1000mH)
,
9999
02160 or
more
0 to 3600m
Ω
(0 to 400mH)
,
9999
462
Second motor constant
(X)
9999
01800 or
less
0 to 500
Ω
(0 to 100%)
,
9999
02160 or
more
0 to 100
Ω
(0 to 100%)
,
9999
463
Second motor auto
tuning setting/status
0
0
Second motor auto tuning is not performed
1
Offline auto tuning is performed without
second motor running
101
Offline auto tuning is performed with
second motor running
684
Tuning data unit
switchover
0
0
Internal data converted value
1
Displayed in "A,
Ω
, mH, %"
Parameter
Number
Name
Initial
Value
Setting Range
Description