Selection of operation mode and operation location
(11) Switching of operation mode by external terminal (X65, X66 signal)
⋅
When
Pr. 79
= any of "0, 2, 6, 7", the operation mode switching signals (X65, X66) can be used to change the PU or
external operation mode to network operation mode during a stop (during a motor stop or start command off). (
Pr.
79
= "6" switch-over mode can be changed during operation)
⋅
When switching between the network operation mode and PU operation mode
1) Set
Pr. 79
to "0" (initial value), "6" or "7". (At the
Pr. 79
setting of "7", the operation mode can be switched when the X12
(MRS) signal turns on.)
2) Set "10 or 12" in
Pr. 340 Communication startup mode selection
.
3) Set "65" in any of
Pr. 178 to Pr. 189
to assign the NET-PU operation switchover signal (X65) to the external terminal.
4) The operation mode changes to PU operation mode when the X65 signal turns on, or to network operation mode
when the X65 signal turns off.
⋅
When switching between the network operation mode and external operation mode
1)Set
Pr. 79
to "0" (initial value), "2", "6" or "7". (At the
Pr. 79
setting of "7", the operation mode can be switched when the
X12 (MRS) signal turns on.)
2)Set "0 (initial value), 1 or 2" in
Pr. 340 Communication startup mode selection
.
3)Set "66" in any of
Pr. 178 to Pr. 189
to assign the NET-external operation switchover signal (X66) to the external terminal.
4)The operation mode changes to network operation mode when the X66 signal turns on, or to external operation mode
when the X66 signal turns off.
Pr. 340
Setting
Pr. 79
Setting
X65 Signal State
Remarks
ON (PU)
OFF (NET)
10, 12
0
(initial value)
PU operation mode
*1
NET operation mode
*2
Cannot be switched to external operation mode
1
PU operation mode
Fixed to PU operation mode
2
NET operation mode
Fixed to NET operation mode
3, 4
External/PU combined operation mode
External/PU combined mode fixed
6
PU operation mode
*1
NET operation mode
*2
Operation mode can be switched with operation continued
Cannot be switched to external operation mode
7
X12(MRS)
ON
PU operation mode
*1
NET operation mode
*2, 3
Output stop in external operation mode
X12(MRS)
OFF
External operation mode
Forcibly switched to external operation mode
*1
NET operation mode when the X66 signal is on.
*2
PU operation mode when the X16 signal is off. PU operation mode also when
Pr. 550 NET mode operation command source selection
= "1"
(communication option control source) and the communication option is not fitted.
*3
External operation mode when the X16 signal is on.
Pr. 340
Setting
Pr. 79
Setting
X66 Signal State
Remarks
ON (NET)
OFF(external)
0
(initial
value)
,
1, 2
0
(initial value)
NET operation mode
*1
External operation mode
*2
1
PU operation mode
Fixed to PU operation mode
2
NET operation mode
*1
External operation mode Cannot be switched to PU operation mode
3, 4
External/PU combined operation mode
External/PU combined mode fixed
6
NET operation mode
*1
External operation mode
*2
Operation mode can be switched with operation continued
7
X12(MRS)
ON
NET operation mode
*1
External operation mode
*2
Output stop in external operation mode
X12(MRS)
OFF
External operation mode
Forcibly switched to external operation mode
*1
PU operation mode is selected when
Pr. 550 NET mode operation command source selection
= "1" (communication option control source) and the
communication option is not fitted.
*2
PU operation is selected when the X16 signal is off. When the X65 signal has been assigned, the operation mode changes with the ON/OFF
state of the X65 signal.
REMARKS
⋅
The priorities of
Pr. 79
,
Pr. 340
and signals are
Pr. 79
>
X12
>
X66
>
X65
>
X16
>
Pr. 340
.
CAUTION
⋅
Changing the terminal assignment using
Pr. 178 to Pr. 189 (input terminal function selection)
may affect the other functions. Please
make setting after confirming the function of each terminal.
♦
Parameters referred to
♦
Pr. 15 Jog frequency
Refer to page 162
Pr. 4 to 6, Pr. 24 to 27, Pr. 232 to Pr. 239 Multi-speed operation
Refer to page 160
Pr. 75 Reset selection/disconnected PU detection/PU stop selection
Refer to page 295
Pr. 161 Frequency setting/key lock operation selection
Refer to page 381
Pr. 178 to Pr. 189 (input terminal function selection)
Refer to page 222
Pr. 190 to Pr. 196 (output terminal function selection)
Refer to page 230
Pr. 340 Communication startup mode selection
Refer to page 309
Pr. 550 NET mode operation command source selection
Refer to page 310