Connection of stand-alone option units
2
W
IRING
(2) Connection with the MT-HC (02160 or more)
*1
Remove the jumper across terminals R/L1 - R1/L11, S/L2 - S1/L21 of the inverter, and connect the control circuit power
supply to the R1/L11 and S1/L21 terminals. The power input terminals R/L1, S/L2, T/L3 must be open. Incorrect connection
will damage the inverter. (E.OPT (option alarm) will occur. (
Refer to page 402.
)
*2
Do not insert the MCCB between terminals P/+
−
N/- (P
−
P/+, N
−
N/-). Opposite polarity of terminals N, P will damage the
inverter.
*3
Use
Pr. 178
to
Pr. 189
(input terminal function selection)
to assign the terminals used for the X10 (X11) signal. (
Refer to page
222.)
For communication where the start command is sent only once, e.g. RS-485 communication operation, use the X11
signal when making setting to hold the mode at occurrence of an instantaneous power failure.
(
Refer to page 199.)
*4
Connect the power supply to terminals R1 and S1 of the MT-HC via an insulated transformer.
CAUTION
⋅
The voltage phases of terminals R/L1, S/L2, T/L3 and terminals R4, S4, T4 must be matched.
⋅
Use sink logic when the MT-HC is connected. The MT-HC cannot be connected when source logic (factory setting) is selected.
⋅
When connecting the inverter to the MT-HC, do not connect the DC reactor provided to the inverter.
Three-phase
AC power
supply
MCCB
MT-HCL01
MT-HCB
R1
S1
R1 S1
R1/
L11
S1/
L21
MT-HCL02
MT-HC
Inverter
MT-HCTR
Insulated transformer
R
S
T
R/L1
S/L2
T/L3
U
V
W
R2
S2
T2
R2
S2
T2
R3
S3
T3
R3
S3
T3
R4
S4
T4
R4
S4
T4
R
S
T
88R
88S
88R
88S
*2
RDY
RSO
SE
X10
RES
SD
*3
*1
*1
*4
Motor
IM
P
N
P/+
N/