196
Motor brake and stop operation
(3) Operation voltage (torque) setting
(Pr. 12)
⋅
Use
Pr. 12
to set the percentage to the power supply voltage. (This parameter is not used during zero speed control
or servo lock.)
⋅
When
Pr. 12
= "0%", the DC injection brake is not operated. (At a stop, the motor coasts.)
⋅
When using the constant-torque motor (SF-JRCA) and energy saving motor (SF-HR, SF-HRCA), change the
Pr. 12
setting as follows.
SF-JRCA: 00126 or less ...4%, 00170 to 01800...2%
SF-HR, SF-HRCA: 00126 or less...4%, 00170, 00250...3%, 00310 to 01800...2%
(00770...1.5%)
(4) Brake operation selection during real sensorless vector control
(Pr. 850)
⋅
You can select DC injection brake (initial value) or zero speed control for brake operation during real sensorless
vector control.
When
Pr. 850
= "1", zero speed control is exercised when the frequency reaches or decreases below the frequency
set in
Pr. 10
.
(5) Brake operation selection under vector control
(Pr. 802)
⋅
When pre-excitation is performed, select zero speed control or servo lock using
Pr. 802
.
⋅
The relationship between the DC injection brake operation and pre-excitation operation under each control
REMARKS
⋅
For the 00170 and 00250, when the
Pr. 12
setting is as below, changing the
Pr. 71 Applied motor
setting changes the
Pr. 12
setting automatically, it is not necessary to change the
Pr. 12
setting.
(a)When
Pr. 12
is 4% (initial value)
The
Pr. 12
setting is automatically changed to 2% if the
Pr. 71
value is changed from the value selecting the standard motor
(0, 2 to 8, 20, 23, 24, 40, 43, 44) to the value selecting the constant torque motor (1, 13 to 18, 50, 53, 54).
(b)When
Pr. 12
is 2%
The
Pr. 12
setting is automatically changed to 4% (initial value) if the
Pr. 71
value is changed from the value selecting the
constant torque motor (1, 13 to 18, 50, 53, 54) to the value selecting the standard motor (0, 2 to 8, 20, 23, 24, 40, 43, 44).
REMARKS
⋅
When the X13 signal is on with
Pr. 11
= "8888", zero speed control is activated regardless of setting of
Pr. 850
Brake operation
selection
.
⋅
When restarting from brake operation during real sensorless vector control, set "1" (zero speed control) in
Pr. 850
. When the
setting value is "0" (DC injection brake), it may take approx. 2s until frequency is actually output from when the start command
is input.
Pr. 802
Setting
Pre-excitation
Description
0 (initial value)
Zero speed control
Even under load, an attempt is made to maintain 0r/min to keep the motor shaft stopped. Note that
if the shaft is overcome and turned by external force, it does not return to the original position.
Position control is not exercised and only speed control is carried out to perform operation.
1
Servo lock
Even under load, an attempt is made to maintain the motor shaft position. Note that if the shaft is
turned by external force, it returns to the original position after the external force has gone away.
Since position control is exercised, you can adjust this position loop gain using
Pr. 422 Position loop gain
.
Control Method
Control Mode
Pr. 802
Pr. 850
Decelerates to Stop
LX-ON
X13-ON
(
Pr. 11
= "8888")
V/F control
⎯
⎯
⎯
DC Injection brake
⎯
DC Injection brake
Advanced magnetic flux
vector control
⎯
⎯
⎯
DC Injection brake
⎯
DC Injection brake
Real sensorless vector
control
Speed
⎯
0
DC Injection brake
Zero speed
Zero speed
⎯
1
Zero speed
Torque
⎯
0
DC Injection brake
Zero speed
Zero speed
⎯
1
Zero speed
Vector control
Speed
0
⎯
Zero speed
Zero speed
Zero speed
1
⎯
Servo lock
Servo lock
Servo lock
Torque
⎯
⎯
Zero speed
Zero speed
Zero speed
Position
⎯
⎯
⎯
Servo lock
⎯
Содержание FR-A740-00023-EC