342
Communication operation and setting
Real-time monitor
Refer to
page 244
for details of the monitor description.
*1
Input terminal monitor details
*2
Output terminal monitor details
*3
Details of option input terminal monitor 1 (input terminal status of FR-A7AX)-all terminals are off when an option is not fitted
*4
Details of option input terminal monitor 2 (input terminal status of FR-A7AX)-all terminals are off when an option is not fitted
*5
Details of option input terminal monitor (output terminal status of FR-A7AY/A7AR)-all terminals are off when an option is not fitted
b15
b0
⎯
⎯
⎯
⎯
CS
RES
STOP
MRS
JOG
RH
RM
RL
RT
AU
STR
STF
b15
b0
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
ABC2
ABC1
FU
OL
IPF
SU
RUN
b15
b0
X15
X14
X13
X12
X11
X10
X9
X8
X7
X6
X5
X4
X3
X2
X1
X0
b15
b0
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
DY
b15
b0
⎯
⎯
⎯
⎯
⎯
⎯
RA3
RA2
RA1
Y6
Y5
Y4
Y3
Y2
Y1
Y0
*6
The setting depends on capacities. (01800 or less / 02160 or more)
Register
Definition
Increments
40201 Output frequency
0.01Hz
40202 Output current
0.01A/
0.1A
*6
40203 Output voltage
0.1V
40205 Frequency setting
0.01Hz
40206 Running speed
1r/min
40207 Motor torque
0.1%
40208
Converter output
voltage
0.1V
40209
Regenerative brake
duty
0.1%
40210
Electronic thermal
relay function load
factor
0.1%
40211
Output current peak
value
0.01A/
0.1A
*6
40212
Converter output
voltage peak value
0.1V
40213 Input power
0.01kW/
0.1kW
*6
40214 Output power
0.01kW/
0.1kW
*6
40215
Input terminal
status
*1
⎯
40216
Output terminal
status
*2
⎯
40217 Load meter
0.1%
40218
Motor excitation
current
0.01A/
0.1A
*6
40219 Position pulse
⎯
40220
Cumulative
energization time
1h
40222 Orientation status
⎯
40223
Actual operation
time
1h
40224 Motor load factor
0.1%
40225 Cumulative power
1kWh
Register
Definition
Increments
40226 Torque command
0.1%
40227
Torque current
command
0.1%
40228 Motor output
0.01/
0.1kW
*6
40229 Feedback pulse
⎯
40250 Power saving effect Variable
40251
Cumulative saving
power
Variable
40252 PID set point
0.1%
40253
PID measured
value
0.1%
40254 PID deviation value
0.1%
40258
Option input
terminal status1
*3
⎯
40259
Option input
terminal status2
*4
⎯
40260
Option output
terminal status
*5
⎯
Register
Definition
Increments