140
Adjust the output torque of the motor (current)
4.8.2
Advanced magnetic flux vector control (Pr. 71, Pr. 80, Pr. 81, Pr. 89, Pr. 450,
Pr. 451, Pr. 453, Pr. 454, Pr. 569, Pr. 800)
* Use
Pr. 178 to Pr. 189
to assign the terminals used for the X18 and MC signal.
(Refer to page 222 )
Advanced magnetic flux vector control can be selected by setting the capacity, number and type of motor to be
used in
Pr. 80
and
Pr. 81
.
What is advanced magnetic flux vector control?
The low speed torque can be improved by providing voltage compensation so that the motor current which
meets the load torque to flow. Output frequency compensation (slip compensation) is made so that the motor
actual speed approximates a speed command value. Effective when load fluctuates drastically, etc.
Parameter
Number
Name
Initial
Value
Setting Range
Description
71
Applied motor
0
0 to 8, 13 to 18,
20, 23, 24, 30, 33, 34, 40,
43, 44, 50, 53, 54
By selecting a standard motor or constant
torque motor, thermal characteristic and motor
constants of each motor are set.
80
Motor capacity
9999
01800 or less 0.4 to 55kW
Set the applied motor capacity.
02160 or
more
0 to 3600kW
9999
V/F control
81
Number of motor poles
9999
2, 4, 6, 8, 10
Set the number of motor poles.
12, 14, 16, 18, 20
X18 signal-ON:V/F control
*
Set 10 + number
of motor poles.
9999
V/F control
89
Speed control gain
(magnetic flux vector)
9999
0 to 200%
Motor speed fluctuation due to load fluctuation
is adjusted during advanced magnetic flux
vector control.
100% is a referenced value.
9999
Gain matching with the motor set in
Pr. 71
.
450
Second applied motor
9999
0 to 8, 13 to 18,
20, 23, 24, 30, 33, 34, 40,
43, 44, 50, 53, 54
Set when using the second motor.
(same specifications as
Pr. 71
)
9999
Function invalid (
Pr. 71
is valid)
451
Second motor control
method selection
9999
10, 11, 12
Real sensorless vector control
20, 9999
V/F control (advanced magnetic flux vector
control)
453
Second motor capacity
9999
01800 or less 0.4 to 55kW
Set the capacity of the second motor.
02160 or
more
0 to 3600kW
9999
V/F control
454
Number of second motor
poles
9999
2, 4, 6, 8, 10
Set the number of poles of the second motor.
9999
V/F control
569
Second motor speed
control gain
9999
0 to 200%
Second motor speed fluctuation due to load
fluctuation is adjusted during advanced
magnetic flux vector control.
100% is a referenced value.
9999
Gain matching with the motor set in
Pr. 450
.
800
Control method selection
20
0 to 5
Vector control
9
Vector control test operation
10, 11, 12
Real sensorless vector control
20
V/F control (advanced magnetic flux vector
control)
POINT
If the following conditions are not satisfied, select V/F control since malfunction such as insufficient torque and
uneven rotation may occur.
• The motor capacity should be equal to or one rank lower than the inverter capacity. (note that the capacity should
be 0.4kW or more)
• Motor to be used is either Mitsubishi standard motor (SF-JR, SF-HR two-pole, four-pole, six-pole 0.4kW or more)
or Mitsubishi constant torque motor (SF-JRCA, SF-HRCA four-pole 0.4kW to 55kW). When using a motor other
than the above (SF-TH, other manufacturer's motors, etc.), perform offline auto tuning without fail.
• Single-motor operation (one motor run by one inverter) should be performed.
• The wiring length from inverter to motor should be within 30m. (Perform offline auto tuning in the state where
wiring work is performed when the wiring length exceeds 30m.)
• For 02160 or more, do not use an option sine wave filter (MT-BSL/BSC) between the inverter and motor.
Magnetic flux
Magnetic flux
Magnetic flux