183
Selection and protection of a motor
4
P
ARAME
T
E
R
S
859
Torque current
9999
01800 or
less
0 to 500A
Tuning data
(The value measured by offline auto
tuning is automatically set.)
02160 or
more
0 to 3600A
9999
Use the Mitsubishi motor (SF-JR, SF-
HR, SF-JRCA, SF-HRCA, SF-V5RU)
constants
860
Second motor torque
current
9999
01800 or
less
0 to 500A
Tuning data of the second motor
(The value measured by offline auto
tuning is automatically set.)
02160 or
more
0 to 3600A
9999
Use the Mitsubishi motor (SF-JR, SF-
HR, SF-JRCA, SF-HRCA, SF-V5RU)
constants
POINT
·
This function is made valid only when a value other than "9999" is set in
Pr. 80
and
Pr. 81
and advanced magnetic
flux vector control, real sensorless vector control or vector control is selected.
·
You can copy the offline auto tuning data (motor constants) to another inverter with the PU (FR-DU07/FR-PU07).
·
Even when motors (other manufacturer's motor, SF-JRC, SF-TH, etc.) other than Mitsubishi standard motor, high
efficiency motor (SF-JR SF-HR 0.4kW or more), Mitsubishi constant-torque motor (SF-JRCA SF-HRCA four-pole
0.4kW to 55kW) and vector control dedicated motor (SF-V5RU) are used or the wiring length is long, using the
offline auto tuning function runs the motor with the optimum operating characteristics.
·
Tuning is enabled even when a load is connected to the motor. (As the load is lighter, tuning accuracy is higher.
Tuning accuracy does not change even if the inertia is large.)
·
For the offline auto tuning, you can select either the motor non-rotation mode (
Pr. 96
= "1") or rotation mode (
Pr. 96
= "101").
·
The rotation mode has higher tuning accuracy than the non-rotation mode.
·
Reading/writing/copy of motor constants tuned by offline auto tuning are enabled.
·
The offline auto tuning status can be monitored with the PU (FR-DU07/FR-PU07/FR-PU04).
· Do not connect a surge voltage suppression filter (FR-ASF-H) to the 01800 or less and sine wave filter (MT-BSL/BSC) to
the 02160 or more between the inverter and motor.
Parameter
Number
Name
Initial
Value
Setting Range
Description