4. AnSHCPU MODULE
4 - 12
MELSEC-A
Table 4.4 Parameter setting ranges (Continued)
Setting
Default value
Setting range
Valid peripheral
devices
Item
PU
GPP
A2SHCPU
X0 to 1FF
(in units of 16 points)
A2SHCPU-S1
X0 to 3FF
(in units of 16 points)
A1SJHCPU(S8)
A1SHCPU
Y0 to FF
(in units of 16 points)
Setting of link
range
Output (Y)
A2SHCPU
None
Y0 to 1FF
(in units of 16 points)
{
A2SHCPU-S1
Y0 to 3FF
(in units of 16 points)
Link relay (B)
B0 to B3FF
(in units of 16 points)
Link register (W)
W0 to W3FF
(in units of 1 point)
I/O assignment
None
X/Y0 to X/Y1FF
(in units of 16 points)
{
Setting of internal relay (M), latch relay (L), and step
relay (S) setting
M0 to M999
L1000 to L2047
None for S
M/L/S 0 to 2047
(M, L, S are serial numbers)
{
{
Watchdog timer setting
200 msec
10 msec to 2000 msec
(in units of 10 msec)
{
{
Setting of timer
100 msec :
T0 to T199
10 msec :
T200 to T255
256 points of 100 msec, 10
msec, and integrating timers
(in units of 8 points).
Timers have serial numbers.
{
{
Setting of counter
No interrupt counter
256 points (in units of 8 points)
for counters and interrupt
counters.
Must be consecutive numbers.
{
A1SJHCPU(S8)
A1SHCPU
X0 to XFF
A2SHCPU
X0 to X1FF
{
A2SHCPU-S1
X0 to X3FF
Fuse blown
Continuation
I/O verify error
Stop
{
Operation error
Continuation
Special function module check error
Stop
STOP
→
RUN display mode
Operation status
prior to re-output of
STOP
Output before STOP or after
operation execution
{
Print title entry
None
Up to 128 characters
{
Keyword entry
None
Max. 6 digits in hexadecimal
(0 to 9, A to F)
{
{
*
It is not possible to set a PAUSE contact alone.
Input (X)
None
Setting of remote RUN/PAUSE
contact *
Operation mode
at the time of
error
Stop/continuation