4. AnSHCPU MODULE
4 - 4
MELSEC-A
Start up
Initial screen
I/O module initialization
Data memory initialization
I/O module I/O address assignment
Self-diagnosis check
Link parameter set
I/O module refresh
If the refresh mode for I/O control is selected.
Sequence program processing
Step 0
to
END (FEND)
instruction execution
END processing
Self-diagnosis check
T/C present values updated and contacts
turned ON/OFF
Communication with conputer link modules
Link refresh
Sampling trace
Fig.4.1 AnSHCPU operation processing
POINT
If a FROM or TO instruction is executed to the special function module
frequently with short scanning intervals, the special function module may not
be processed normally.
When you execute a FROM or TO instruction to the special function module,
adjust the processing time and conversion time using the timer, constant scan
and other measures of the special function module.