9. EMC DIRECTIVE AND LOW-VOLTAGE INSTRUCTION
9 - 5
MELSEC-A
(3) Ethernet module, Web server module
Precautions for using AUI cables, twisted pair cables and coaxial cables are
described below.
(a) Always earth the AUI cables connected to the 10BASE5 connectors.
Because the AUI cable is of the shielded type, strip part of the outer cover
and earth the exposed shield section to the ground on the widest contact
surface as shown below.
AUI cable
Shield
Refer to (1) for the earthing of the shield.
(b) Use shielded twisted pair cables as the twisted pair cables connected to the
10BASE-T/100BASE-TX connectors. For the shielded twisted pair cables,
strip part of the outer cover and earth the exposed shield section to the
ground on the widest contact surface as shown below.
Shielded twisted pair cables
Shield
Refer to (1) for the earthing of the shield.
(c) Always use double-shielded coaxial cables as the coaxial cables connected
to the 10BASE2 connectors. Earth the double-shielded coaxial cable by
connecting its outer shield to the ground.
Earth here
Shield
Refer to (1) for the earthing of the shield.
Ethernet is the registered trademark of XEROX Corporation in the US.
(4) I/O and other communication cables
Always earth the shield section of the I/O signal cables and other communication
cables (RS-232-C, RS-422, etc.) in the same manner as described in (1) if the
cables go outside of the control cabinet.