9. EMC DIRECTIVE AND LOW-VOLTAGE INSTRUCTION
9 - 6
MELSEC-A
(5) Positioning Modules
(a)
When wiring with a 2 m (6.6 ft.) or less cable
Ground the shield section of the external wiring cable with the cable
clamp.
(Ground the shield at the closest location to the A1SD75 external wiring
connector.)
Wire the external wiring cable to the drive unit and external device with
the shortest distance.
Install the drive unit in the same panel.
Pow
e
r s
u
p
p
ly
mod
u
le
CP
U m
o
du
le
A1S
D
7
5
mod
u
le
Drive unit
External wiring connector
External wiring cable (within 2 m (6.56 ft.))
Cable clamp
(b)
When wiring with cable that exceeds 2 m (6.6 ft.), but is 10 m (32.8 ft.)
or less
Ground the shield section of the external wiring cable with the cable
clamp.
(Ground the shield at the closest location to the A1SD75 external wiring
connector.)
Install a ferrite core.
Wire the external wiring cable to the drive unit and external device with
the shortest distance.
Pow
e
r s
u
p
p
ly
modul
e
CP
U
mod
u
le
A1SD
75
modul
e
Drive unit
External wiring connector
Ferrite core
External wiring cable (2 m to 10 m (6.56 ft. to 32.81 ft.))
Cable clamp
(c)
Ferrite core and cable clamp types and required quantities
•
Cable
clamp
Type : AD75CK (Mitsubishi Electric)
•
Ferrite
core
Type : ZCAT3035-1330 (TDK ferrite core)
•
Required
quantity
Required Qty
Cable length
Prepared part
1 axis
2 axes
3 axes
Within 2 m (6.6 ft.)
AD75CK
1
1
1
2m (6.6 ft.) to 10m
AD75CK
1
1
1
(32.8 ft.)
ZCAT3035-1330
1
2
3
Содержание A1SH