APPENDICES
APP - 12
MELSEC-A
Table 2.1
Special relay list (Continue)
Number
Name
Description
Details
Applicable CPU
M9077
Sequence
accumulation
time
measurement
OFF: Time not elapsed
ON: Time elapsed
• Compares the setting value at D9077 with the time
elapsed from the start of measurement
(accumulation time) at every scan. Then, performs
the following operations:
Setting value > Accumulation time:
Turns M9077 ON and clears the accumulation
time.
Setting value < Accumulation time:
Turns M9077 from ON to OFF and clears the
accumulation time. When M9077 is already OFF,
clears the accumulation time.
When 1 to 255 is designated at D9077, M9077 is
turned ON at the first scan.
When the value other than 1 to 255 is designated
at D9077, the value in D9077 is reset to 0 and
M9077 is always turned OFF.
—
Dedicated to
QCPU-A (A Mode)
M9078
Test mode
request error flag
OFF: No error
ON: Error
• Turned on when test mode is not available though a
test mode request was made from a peripheral
device. Turned off if test mode becomes available by
making another test mode request.
—
Dedicated to A73.
M9079
Servo program
setting error flag
OFF: No data error
ON: Data error
• Turned on when the positioning data of the servo
program designated by the DSFRP instruction has
an error.
Turned off when the data has no error after the
DSFRP instruction is executed again.
—
Dedicated to A73.
Turned ON/OFF according to the number of remaining
instructions ( RIRD / RIWT / RISEND / RIRCV )
being executable simultaneously at one scan.
OFF: Number of remaining instructions executable
simultaneously: 1 to 10
ON: Number of remaining instructions executable
simultaneously: 0
By assigning M9080 as execution condition, the
number of instructions above executed simultaneously
at one scan can be limited to 10 or less.
4: This function is available with the CPU of the
following S/W versions or later.
CPU Type Name
Software Version
Q02CPU-A, Q02HCPU-A,
Q06HCPU-A
A1SJHCPU, A1SHCPU,
A2SHCPU
Available with all versions
A2UCPU(S1), A3UCPU,
A4UCPU
S/W version Q (Manufactured
in July, 1999)
A2USCPU(S1)
S/W version E
(Manufactured in July, 1999)
A2USHCPU-S1
S/W version L
(Manufactured in July, 1999)
M9080
BUSY flag for
execution of CC-
Link dedicated
instruction
OFF: Number of
remaining
instructions
executable
simultaneously:
1 to 10
ON: Number of
remaining
instructions
executable
simultaneously: 0
Can be used only
with AnU, A2US, or
AnSH, QCPU-A
(A Mode)
4
Содержание A1SH