Using an AGS Module: Operation
©
2017 Sensata Technologies
Page 103
Table 8-4, AGS Router Start Statuses
Status
Description
Start Amp
(StrtAmp or SAmp)
The generator has started based on the
SETUP: 04C Gen Run AC Amps
settings.
Start Exercise
(StrtExe or SExe)
The generator has started based on the
SETUP: 04H
Gen Exercise
settings.
Start SOC
(StrtSOC or SSOC)
The generator has started based on the
SETUP: 04D Gen Run SOC
setting.
Start Temp
(StrtTemp or STmp)
The generator has started based on the
SETUP: 04E Gen Run Temp
setting.
Start Test
(StrtTest or STst)
The AGS is in Test mode. Test mode may be started from the TEST
button located on the AGS.
Start Time Daily
(StrtTOD or STOD)
The generator has started based on the
SETUP: 04B Gen Run Time
setting.
Start Topoff
(StrtToff or STop)
The generator has started based on the
SETUP: 04G Gen Quiet Time
menu’s
Topoff
time setting.
Start VDC
(StrtVDC or SVDC)
The generator either has started based on the
SETUP: 04A Gen Run Volts
DC
settings, or was manually started and then set to AUTO to autostart.
Start 100% SOC
(Strt100% or S100)
The generator has started based on the
SETUP: 04J Gen 100% SOC
settings.
8.2.6.3
AGS Router Fault Statuses
The following “Fault” statuses indicate that the generator wasn’t able to start based on an expected
autostart condition. Refer to Section 8.3.2 “Resolving AGS Faults using your Router” for help in
diagnosing the problem.
Table 8-5, AGS Router Fault Statuses
Status
Description
Fault Amp
(Falt Amp or FAmp)
The generator failed to start in Start Amps mode.
Fault Exercise
(Falt Exe or FExe)
The generator failed to start in Start Exercise mode.
Fault Gen Run
(FaltGnRn or FGnR)
The generator successfully started and ran for more than two minutes,
but unexpectedly stopped before the AGS could automatically stop the
generator.
Fault MaxRn
(FaltMxRn or FMxR)
The generator has run longer than expected and has met or exceeded
the
SETUP: 04F Max Gen Run Time
setting. This fault can occur when:
1) an autostop condition has been met, but the AGS was not able to stop
the generator; or, 2) the autostop setting exceeded the
Max Gen Run
Time
setting.
Fault SOC
(Falt SOC or FSOC)
The generator failed to start in Start SOC mode.
8.2.6.2
AGS Router Start Statuses
The following “Start” statuses identify the condition that autostarted the generator. If you
determine the autostart condition occurred sooner than expected (or didn’t want this autostart
condition), refer to Section 8.1 to change (or defeat) the autostart setting.