Operation
Page 60
©
2017 Sensata Technologies
FAULT
PWR
CHG
INV
Constant Current
Settings/Info...
Constant Current
appears on LCD. PWR (green) and
CHG (green) LEDs are on solid. FAULT (red) LED is
off, and INV (green) LED could be on or off.
Figure 5-14, Constant Current Mode
• Constant
Current
(CCurrent)
– The battery charger is delivering maximum current to the
batteries (determined by the
Max Charge Amps
setting under the SETUP button’s
03C Battery
Type: CC/CV
menu). The charger remains in Constant Current charge until the
CV Charge Volts
or
Max CC/CV Charge Time
is reached (determined by the settings under the SETUP button’s
03C
Battery Type: CC/CV menu
).
Note:
This status only displays if “CC/CV” has been selected from the SETUP button’s 03C Battery
Type menu.
Constant Voltage
appears on LCD. PWR (green) and
CHG (green) LEDs are on solid. FAULT (red) LED is off,
and INV (green) LED could be on or off.
FAULT
PWR
CHG
INV
Constant Voltage
Settings/Info...
Figure 5-15, Constant Voltage Mode
• Constant Voltage (CVoltage)
– This mode begins when the
CV Ch Volts
is reached
(determined by the settings under the SETUP button’s
03C Battery Type: CC/CV
menu) while in
the Constant Current charge mode. During this stage, the DC charging current decreases in order
to maintain the absorb voltage setting. This charge stage continues until the
03D Absorb Done
(
Time
,
Amps
, or
SOC
) or
03E Max Charge: Time
setting is reached.
Note:
This status only displays if “CC/CV” has been selected from the SETUP button’s 03C Battery
Type menu.
Equalizing
appears on LCD. PWR (green) and CHG
(green) LEDs are on solid. FAULT (red) LED is off, and
INV (green) LED could be on or off.
• Equalizing
(Equalize)
– This display indicates the charger is delivering the equalize voltage
to the batteries based on the equalize voltage from Table 3-1 for your battery type.
Equalize charging can be enabled by the ON/OFF CHARGER button—if the SETUP button’s
03C
Battery Type
setting allows. Equalization charging can only be enabled while the charger is in
Float Charge, Full Charge, or Silent Charge mode. To turn on Equalize charging, ensure the LCD
display reads
“Float Charging”
,
“Full Charge”
or
“Silent”
, and then press and hold down the ON/
OFF CHARGER button (about 5 seconds) until the LCD screen displays
“Equalizing”
.
The Equalize charge continues for four hours and then automatically stops and returns to the
previous charge mode. The Equalize charge can be manually stopped by pressing and holding
down the ON/OFF CHARGER button (about 5 seconds) until the LCD screen leaves
“Equalizing”
and then leaves “
Charger Standby
” and shows the previous charge mode (i.e., Float Charge, Full
Charge, or Silent Charge mode).
WARNING:
Equalizing produces hydrogen and oxygen gas. To avoid explosions, ensure
the battery compartment has adequate ventilation in order to dissipate this gas.
FAULT
PWR
CHG
INV
Equalizing
Settings/Info...
Figure 5-16, Equalizing Mode