Setup
Page 14
©
2017 Sensata Technologies
3.3.2
CTRL (Control) Button and Menus
The CTRL button accesses the
01 AC In Control
,
02
Charger Control
,
03
Gen Control, and 04 ARTR
Aux Relay
menus.
Info:
An AGS must be connected in order for the
Gen Control
menu to display unless
the
TECH: 08 Show all Menus
menu has been set to “
YES
”. Refer to
page 47 for more
info on the
TECH 08
menu. Otherwise, “
No AGS Present
” appears on the
03 Gen Control
screen.
The CTRL button gives you quick control of the main functions of the inverter/charger without
having to access the SETUP button’s menus in order to change the operation of the inverter/
charger or the generator. Once the settings have been programmed in the SETUP menus, the
features can then be enabled using the CTRL button.
Example:
The SETUP menu’s
02C AC In – Time
setting sets what time of day (e.g., 12AM to 8AM)
you want the inverter to connect to the incoming AC. Once this time is set, use the CTRL button to
access the
Set
AC In Control
menu item and select
Time Connect
. When
Time Connect
is selected,
the inverter/charger connects to AC when the time is between 12AM and 8AM.
Press to
edit setting
Press
CTRL
Rotate &
press to
select:
Top lines show menus
Bottom line shows view
01 AC In Control
02 Charger Control
03 Gen Control
ALL Select CTRL
01 AC In Control
Auto Connect
ALL View ACI CTRL
Multi-Stage
Start Float
Start Bulk
02 Charger Control
Multi-Stage
ALL View CHG CTRL
Auto Connect
VDC Connect
Time Connect
SOC Connect
AC In - Disabled
03 Gen Control
OFF
ALL Read AGS CTRL
OFF
ON
AUTO
04 ARTR Aux Relay
Force Open
ALL View SYS CTRL
Force Open
Force Closed
Auto VDC
Auto VDC (BTS Comp)
Auto Fault
Auto SOC
05A PT Chg Ctrl x7
Multi-Stage
[Chg Mode]
SYS View PT CTRL
05A PT Chg Ctrl
05B PT Aux Relay
05C PT Alarm Ctrl
05D PT MPPT Ctrl
Figure 3-4, CTRL (Control) Button and Menus