Using an AGS Module: Setup
©
2017 Sensata Technologies
Page 85
Why would I use Gen Run AC Amps?
This feature is designed to prevent the battery from
being heavily discharged by monitoring the battery current used to power the inverter loads
(shown in AC amps). When the AC current exceeds the
Start AC Amps
setting, a generator
autostart is initiated. After the generator connects to the inverter, the current from the generator
is now used to run the loads instead of the battery current. This feature is useful when there is
occasionally a large load or combinations of loads that the inverter is able to run, but by doing so
would quickly deplete the battery bank. Typically, these large loads might be motors, well pumps,
A/C units, or freezers.
Info:
The
04C Gen Run AC Amps
feature is not designed to turn on the generator to
power loads above the capacity of the inverter. If attempting to run loads above the
inverter capacity, the inverter may overload and shut down before the generator can
autostart and power the heavy load thru the inverter.
Where should I set Gen Run AC Amps?
Typically, the generator should autostart when the
AC load amps is >70-75% of the inverter AC current output rating
¹
. This keeps the inverter from
running too large a load and also keeps the batteries from cycling unnecessarily. Set
Stop AC
Amps
just below the start amps to ensure the large load has turned off. Set the start delay time
so surge loads don’t trigger a false start, and the stop delay time is long enough to ensure the
load has turned off.
Example:
In this scenario, most AC loads typically do not exceed 20A when in Inverter mode.
When a freezer or well pump starts, the load exceeds 30A so the battery voltage starts to quickly
drop. Instead of cycling the batteries to a low voltage, set
Start AC Amps
to
25A
with a
60-second
delay (using
Start Delay
setting). Set the
Stop AC Amps
menu to
20A
with a
60-second
delay
(using
Stop Delay
setting). After 60 seconds of detecting a larger than 25A load on the inverter,
the generator autostarts and powers the loads and recharges the batteries. Once the AC amps
load drops below 20A for 60 seconds, the gen turns off.
SETUP: 04D Gen Run SOC Menu
This menu starts and stops the generator based on the SOC (State of Charge) reading from the
attached battery monitor, as shown on the METER button’s
05A BMK SOC
display. This is the
best method for using AGS settings to start/stop your generator. Since the ME-BMK already uses
voltage, time, and current to determine the true SOC of the batteries, there is little guesswork or
calculating needed to determine what settings to use.
• Set
Gen Run SOC ( Start SOC)
– This menu sets the SOC level for autostarting the generator.
Default setting:
Start SOC = OFF
Range:
OFF, 20%-99%
• Set
Gen
Run
SOC
(Stop SOC)
– This menu sets the SOC level for autostopping the generator.
Default setting:
Stop SOC = 90%
Range:
21%-100%
Info:
There is no start or stop delay time needed since the ME-BMK already displays an
accurate state of charge of the batteries.
Info:
The optional Battery Monitor Kit (ME-BMK or ME-BMK-NS) must be installed and
enabled to use the
04D Gen Run SOC
autostart/autostop feature.
Info:
When using the
04D Gen Run SOC
autostart/autostop feature, the generator
autostarts and runs until the battery bank has reached the
Stop SOC
setting or the
AGS’s
SETUP: 04F Max Gen Run Time
setting is reached, whichever occurs
fi
rst. Ensure
the charger never leaves the Bulk/Absorption charge mode. This is done by ensuring
the
SETUP: 03 Absorb Done
selection is “
SOC
” and the setting is greater than or equal
to the
Stop SOC
setting; and either set the
Max Gen Run Time
setting to
OFF
, or set it
long enough to ensure the generator is able to run until the battery is fully charged. If
the charger is allowed to exit the Bulk/Absorption charge mode (i.e., go to Float/Silent),
the battery SOC may never reach 100%.
Note
¹
–
For a 4000 watt inverter, this would mean setting Start AC Amps at 25A.