Operation
©
2017 Sensata Technologies
Page 63
5.3.3
Secondary Scrolling Status Messages
These displays alternate with the inverter’s primary status to indicate other pertinent messages.
Note:
Depending on circumstances, the lighting sequence of the LED indicators may vary as there
can be several secondary status messages scrolling at any one time.
FAULT
PWR
CHG
INV
AC In - Disabled
Settings/Info...
AC In – Disabled
appears on LCD. PWR (green) LED
is on solid and CHG (green) LED is blinking.
Figure 5-22, AC In – Disabled Mode
•
AC In – Disabled
– AC power is present at the inverter’s AC input, but the inverter/charger
is prevented from connecting to any incoming AC because the
AC In – Disabled
setting is selected
from the
CTRL: 01 AC In Control
menu.
• Gen
Cooldown
– The ME-AGS-N has commanded a generator to run, but the inverter does
not connect to the generator’s AC output until the generator cooldown time is complete.
Note:
Requires the optional ME-AGS-N Auto Gen Start module to be connected.
FAULT
PWR
CHG
INV
Gen Cooldown
Settings/Info...
Gen Cooldown
appears on LCD. PWR (green) LED is
on solid and CHG (green) LED is blinking.
Figure 5-23, Gen Cooldown Mode
• Gen
Warm-up
– The ME-AGS-N has commanded a generator to run, but the inverter does
not connect to the generator’s AC output until the generator warm-up time is complete.
Note:
Requires the optional ME-AGS-N Auto Gen Start module to be connected.
FAULT
PWR
CHG
INV
Gen Warm-up
Settings/Info...
Gen Warm-up
appears on LCD. PWR (green) LED is
on solid and CHG (green) LED is blinking.
Figure 5-24, Gen Warm-up Mode