CTRL: 02 Charger Control
The
02
Charger Control
menu enables you to set the charge mode to
Multi-Stage
,
Start Float
,
or to
Start Bulk
. Most of the time the charger should be left in the
Multi-Stage
setting, but to
override this setting use the CTRL button and the 02
Charger Control
menu. The charger can be
forced to start the Float or Bulk charge mode using the
Start Float
or
Start Bulk
settings.
•
Multi-Stage:
This charge pro
fi
le causes the charger to automatically operate thru the multi-
stage (Bulk, Absorption, and Final Stage) charge cycles. When AC is connected and the
charge mode begins
¹
, the inverter’s battery voltage is monitored to determine the charging
stage. If the battery voltage is low (
≤
12.8 VDC/12-volt models,
≤
25.6 VDC/24-volt models,
or
≤
51.2/48-volt models), the charger begins Bulk Charging. If the battery voltage is high
(
≥
12.9 VDC/12-volt models,
≥
25.7 VDC/24-volt models, or
≥
51.3/48-volt models), the
charger skips the Bulk and Absorb charge stages and goes directly to the
fi
nal charge stage
(
Multi-Stage
,
Float
, or
Silent
) as selected in the
SETUP: 03F Final Charge Stage
menu item.
Note¹
–
If the
SETUP: 03C Battery Type
selection is
CC/CV
, once AC connects and the charge
mode begins, the charger enters the Constant Current charge mode. If the
CTRL: 01 AC In
Control
setting is “
SOC Connect
,” or if the
SETUP: 03D Absorb Done
setting is “
SOC
”, then the
charger enters the Bulk Charge mode once AC is connected and charging begins.
•
Start Float:
This selection restarts the Float charge cycle from any stage in the charge cycle
as long as the charger is active.
Info:
The
Start Float
selection automatically defaults back to the
Multi-Stage
setting
once the inverter/charger status displays “
Float Charging
” (or “
Silent
” if battery type
CC/CV
is selected).
Info:
If battery type
CC/CV
is chosen, the
Start Float
selection transfers the charger
to Silent mode—unless “
Hold CV Chg Volts
” is selected, then the charger enters the
Constant Current charge mode.
• Start
Bulk:
This selection restarts the Bulk charge cycle from any stage in the charge cycle
as long as AC is present and the charger is active. The
Start Bulk
selection is useful when a
full multi-stage charge cycle does not bring the speci
fi
c gravity of the batteries to the proper
level.
Info:
After
Start Bulk
is selected and activated, the
02 Charger Control
selection
automatically returns back to the
Multi-Stage
setting.
Info:
If the current charge mode is Bulk or Absorption, and
Start Bulk
is selected,
“
Already in Bulk/Abs
” displays on the router.
Info:
If battery type
CC/CV
is chosen, and the charger is in Silent charge mode, the
Start Bulk
selection transfers the charger to Constant Current mode.
Info:
If you have to continually restart the bulk cycle in order to bring the batteries
to full charge, check the settings from the
SETUP:
03 Charger Setup
menu to ensure
the batteries are fully charged at the end of a regular multi-stage charge cycle.
CTRL: 03 Gen Control
03 Gen Control
is used for controlling a standby generator that is connected to the system and
using the optional ME-AGS-N module. For information on these settings, refer to
Section 8.2.1.
CTRL: 04 ARTR Aux Relay
The Aux Relay can be programmed to open or close based on the inverter’s battery voltage, the
battery’s state of charge ( SOC), or used to indicate an inverter fault has occurred.
Note:
Options include: Force Open (default setting), Force Closed, Auto VDC, Auto VDC (BTS
Comp), Auto Fault, and Auto SOC.
Info:
When the relay is open (de-energized), the router’s Aux Relay LED (yellow) is off.
When the relay closes (energized), the relay’s LED is on.