Using an AGS Module: Operation
©
2017 Sensata Technologies
Page 101
Figure 8-4, AGS SETUP Menu Maps (Section 2)
Set Gen Quiet Time
Begin Quiet= 7:00PM
End Quiet =10:00AM
P6 edit AGS SETUP
04G Gen Quiet Time
Begin Quiet= 7:00PM
End Quiet =10:00AM
P6 View AGS SETUP
04H Gen Exercise
Every 100 days at
08:00AM for 10.0 Hrs
P6 View AGS SETUP
Set Gen Exercise
Start Gen Days =100
Start Time =08:00AM
P6 edit AGS SETUP
04I Gen No-Load Time
Warm-up = 60secs
Cooldown = 60secs
P6 View AGS SETUP
P
R
P
R
Set Gen No-Load Time
Warm-up = 60secs
Cooldown = 60secs
P6 edit AGS SETUP
P
P
0.1-25.5 Hrs
AGS SETUP menu continued from previous page
R
P
Set Time to Topoff
Battery before Quiet
Time= 30 Minutes
P6 edit AGS SETUP
OFF, 12:00AM-11:45PM
OFF, 30, 60, 90,120 Mins
Set Gen Exercise
Run Time= 1.0 Hours
P6 edit AGS SETUP
0-127 secs, 1-127 mins
04J Gen 100% SOC
Start Gen if SOC not
100% every 3 Days
P6 View AGS SETUP
Set Gen 100% SOC
Start Gen Days = 3
Start Time = 8:00AM
P6 edit AGS SETUP
P
R
OFF, Days = 1-255
Time
=
12:00AM-11:45PM
OFF, Days = 1-255
Time
=
12:00AM-11:45PM
Menu Button
Default/
Current
Setting
Press SELECT
Knob
Rotate
SELECT
Knob
LEGEND
SETUP
04A Gen Run DC Volts
Start= 23.0V/ 60secs
Stop = 28.8V/120secs
P6 View AGS SETUP
Menu Headings
Menu
Port
Display Type
R
Set Gen Run DC Volts
Start Volts = 23.0V
Stop Volts = 28.8V
P6 edit AGS SETUP
P
Device
Setting
Settings/Range
x2
x2