Setup
©
2017 Sensata Technologies
Page 33
• 03C Battery Type:
This setting selects the battery type, which determines the battery
charge pro
fi
le and ensures the batteries are receiving the proper charge voltage. The charge
voltage settings are
fi
xed when using the
GEL
,
Flooded
,
AGM1
, or
AGM2
selections, but can
be adjusted if using the
CC/CV
or
Custom
selections.
Default setting:
Flooded
Range:
AGM1, AGM2, Flooded, GEL, CC/CV, Custom
◊
Set Battery Type ( GEL, Flooded, AGM1, or AGM2)
– When the battery type selection
is
GEL
(for Gel batteries),
Flooded
(for liquid lead acid batteries),
AGM1
(for Lifeline AGM
batteries), or
AGM2
(for East Penn/Deka/Discover/Trojan AGM batteries), the charge voltage
level for the Absorption, Float, and EQ charge modes are
fi
xed and shown in Table 3-1—
depending on the battery type selected and the nominal inverter battery voltage.
Info:
The voltage settings shown in Table 3-1 are based on the Battery Temperature
Sensor (BTS) at a temperature of 77°F/25°C, or not connected. If the BTS is connected,
the actual charge voltage increases if the temperature around the BTS is below
77°F/25°C, and decreases if higher than 77°F/25°C. This ensures the batteries receive
the correct charge voltage regardless of temperature.
Table 3-1, Battery Type to Charge Voltages
Battery
Type
Inverter
Voltage
Absorption
Voltage
Float
Voltage
Equalization
Voltage
Fixed Voltage
GEL
12 VDC
14.1 VDC
13.6 VDC
14.1 VDC
1
24 VDC
28.2 VDC
27.2 VDC
28.2 VDC
1
48 VDC
56.4 VDC
54.4 VDC
56.4 VDC
1
Flooded
12 VDC
14.6 VDC
13.4 VDC
15.5 VDC
24 VDC
29.2 VDC
26.8 VDC
31.0 VDC
48 VDC
58.4 VDC
53.6 VDC
62.0 VDC
AGM1
2
12 VDC
14.3 VDC
13.1 VDC
15.5 VDC
24 VDC
28.6 VDC
26.2 VDC
31.0 VDC
48 VDC
57.2 VDC
52.4 VDC
62.0 VDC
AGM2
3
12 VDC
14.5 VDC
13.5 VDC
14.5 VDC
1
24 VDC
29.0 VDC
27.0 VDC
29.0 VDC
1
48 VDC
58.0 VDC
54.0 VDC
58.0 VDC
1
Adjustable Voltage
Custom
4
12 VDC
12.0-16.0 VDC
12.0-16.0 VDC
12.0-16.0 VDC
24 VDC
24.0-32.0 VDC
24.0-32.0 VDC
24.0-32.0 VDC
48 VDC
48.0-64.0 VDC
48.0-64.0 VDC
48.0-64.0 VDC
CC/CV
12 VDC
12.0-16.0 VDC
12.0-16.0 VDC
12.0-16.0 VDC
24 VDC
24.0-32.0 VDC
24.0-32.0 VDC
24.0-32.0 VDC
48 VDC
48.0-64.0 VDC
48.0-64.0 VDC
48.0-64.0 VDC
Note¹:
Voltage same as absorption voltage—to prevent equalization.
Note²:
Charge voltages for Concord (Lifeline Series) AGM batteries.
Note³:
Charge voltages for East Penn, Deka, Discover and Trojan AGM batteries.
Note
4
:
When using the Custom setting, the EQ (Equalization) voltage adjustment cannot be
set lower than the Absorb Voltage setting. Also, the EQ Voltage adjustment cannot be set
higher than 2 volts (12-volt systems), 4 volts (24-volt systems), or 8 volts (48-volt systems)
above the Absorb Voltage setting.
Содержание ME-ARTR