Using an AGS Module: Setup
Page 84
©
2017 Sensata Technologies
SETUP: 04B Gen Run Time Menu
This menu starts and stops the generator based on a speci
fi
c time of day. This feature uses the
ME-ARTR’s internal clock to start and stop the generator at the selected times.
Info:
Ensure the router’s clock is correct. Refer to Section 3.3.4 for guidance on setting
the time on the router clock. The ME-ARTR’s clock is powered from the inverter through
the remote cable. If the ME-ARTR or inverter loses power, the clock loses the correct
time and must be reset.
• Set Gen Run Time
(Start Daily)
– This setting allows you to set a time at which the
generator automatically turns on each day. Select
OFF
to disable the Gen Run Time feature.
Default setting:
Start Daily = OFF
Range:
OFF, 12:00AM-11:45PM (15 minute increments)
• Set Gen Run Time (Stop Daily)
– This setting allows you to set a time at which the
generator automatically turns off each day.
Default setting:
Stop Daily = 12:00AM
Range:
12:00AM-11:45PM (15 minute increments)
Why would you want to start/stop the generator daily?
Starting/stopping at a particular
time of day is useful if you want to run the generator for other uses while charging the batteries.
You may require the generator to run a heavy load (like a well pump or machinery) every day at
the same time; or, to run while at work each day to have charged batteries when you get home,
and to avoid having to hear it run.
SETUP: 04C Gen Run AC Amps Menu
This menu starts the generator based on the amount of AC amps needed to handle the inverter
load the inverter is running.
Info:
The METER button’s
02C System AC Amps (AC Load)
menu is used to determine
how much load the inverter is currently running when in Inverter mode.
Info:
The
04C Gen Run AC Amps
menu is only applicable to Magnum’s MS-PAE, MS-PE,
and MSH Series inverters.
• Set
Gen Run AC Amps (Start AC Amps)
– This setting determines when the generator
would start depending on the AC amps level of the load the inverter is running. The load’s
amps level must be continuously maintained above the
Start AC Amps
setting for the duration
of the
Start Delay
setting in order for the generator to autostart.
Default setting:
Start AC Amps = OFF
Range:
OFF, 5-60 Amps
• Set
Amps Delay Time (Start Delay)
– This setting determines the amount of time that the
inverter load’s current must continuously remain above the
Start AC Amps
setting for the AGS
to initiate an autostart.
Default setting:
Start Delay = 120secs
Range:
0-127 Seconds,
then
1-127 Minutes
• Set Gen Run AC Amps (Stop AC Amps)
– This setting determines when the generator
would stop depending on the drop in the AC amps level of the load the inverter is running.
The load’s amps level must be continuously maintained below the
Stop AC Amps
setting for
the duration of the
Stop Delay
setting in order for the generator to autostop.
Default setting:
Stop AC Amps = 4 Amps
Range:
4-59 Amps
• Set Amps Delay Time (Stop Delay)
– This setting determines the amount of time the
AC load must continuously remain below the
Stop AC Amps
setting before the generator
autostops.
Default setting:
Stop Delay = 120secs
Range:
0-127 Seconds,
then
1-127 Minutes